Inspections for the day of: Thursday, October 29, 2015.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01498 ELE-Aging Inspection10/29/201510/29/201510/30/2015 11:28:58 AM DONE
Still under construction
ELE15-02598 Final10/29/201510/29/201510/29/2015 4:35:03 PMPPASS
Final on Walmart. Contact is Jay Sprik. Phone #: ###-#### Inspection requested via web by Richard Montgomery Final ok
ELE15-03466 Electrical Rough-In10/29/201510/29/201510/29/2015 3:40:18 PMPPASS
Underground electrical from transformer to building. Phone #: ###-#### Inspection requested via web by Richard Montgomery As noted rough in ok cover
ELE14-01066 Electrical Rough-In10/29/201510/29/201510/29/2015 3:05:29 PMPPASS
Ceiling grid for tile cover, H building, 3rd floor, Corridors H360, H365, H368 and Rooms H369, H363. Contact Craig Timmons @ ###-#### or Bob Mott Phone #: ###-#### Inspection requested via web by Cathy Duchek Also checked corridor 356, 357. Grid rough in ok cover as noted
ELE14-02371 Final10/29/201510/29/201510/29/2015 3:02:51 PMPPASS
Bldg F Floor 1,2,3 done 10-23-15 Floor 4 don 9-21-15, Bldg G Floor 1,2,3 done 10-27-15. Final ok
ELE15-03309 Final10/28/201510/29/201510/29/2015 1:20:51 PMAFAIL
Jay Phone #: ###-####
110.12- Unused openings shall be closed. 1/2" KO seals above grid boxes.
314.25- All boxes shall be covered.
406.6- All receptacles shall have covers.
ELE15-03461 Permanent Service10/28/201510/29/201510/29/2015 12:43:07 PMAPASS
We Would Like,To Get Permanent Service As,Well As Some Underground To A Future Out Building Please And Thank You Call With Any Questions Or,Concerns. Phone #: ###-#### Inspection requested via web by jason shifflett p/s u/g n ok
ELE15-03461 Electrical Rough-In10/29/201510/29/201510/29/2015 12:42:21 PMPPASS
We Would Like,To Get Permanent Service As,Well As Some Underground To A Future Out Building Please And Thank You Call With Any Questions Or,Concerns. Phone #: ###-#### Inspection requested via web by jason shifflett
Underground to back out building rough in ok cover
ELE15-03484 Conference10/28/201510/29/201510/29/2015 12:29:52 PMADONE
After 10 // Katie Phone #: ###-#### Discussed code requirements for enclosed sun room.
ELE15-03396 Electrical Rough-In10/28/201510/29/201510/29/2015 11:54:04 AMAPASS
We need an underground inspection.
Thank you! Phone #: ###-#### Inspection requested via web by Stacie Tasker Underground to east electrical room and concrete encased electrode rough in ok cover
ELE15-03425 Final10/28/201510/29/201510/29/2015 11:40:06 AMAPASS
Mike Phone #: ###-#### Final ok
ELE15-03425 Electrical Rough-In10/29/201510/29/201510/29/2015 11:39:12 AMPPASS
Mike Phone #: ###-#### Roof AC rough in ok cover
ELE15-03099 Final10/28/201510/29/201510/29/2015 11:17:08 AMAPASS
Phone #: ###-#### Inspection requested via web by Greg Traudt Final ok
ELE15-03409 Rough-In Permanent Service10/29/201510/29/201510/29/2015 10:59:19 AMPPASS
READY NOW Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
ELE15-03503 Rough-In Permanent Service10/28/201510/29/201510/29/2015 10:40:48 AMAFAIL
Phone #: ###-#### Inspection requested via web by TOM BICANDI
110.3- NM cable has damaged insulation up bed front west.
300.4- NM cable shall be protected from physical damage where bored hole does not maintain 1 1/4" from framing surface. Up bed front east under switch.
ELE15-03494 Electrical Rough-In10/28/201510/29/201510/29/2015 10:10:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Bryan Atkins Installed 110 amp outdoor panel on back of store to feed a air system to dry and test contamination underground. Rough in ok
ELE15-00338 Electrical Rough-In10/28/201510/29/201510/29/2015 9:40:48 AMAPASS
Butch Phone #: ###-####
Walls and hardlids all units rough in ok cover