Inspections for the day of: Thursday, October 3, 2002.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00386 INSP-Sprinkler Rough-in/Hydro10/2/200210/3/200210/3/2002 12:00:00 AMAFAIL
provide one additional head and relocate another to match the plans in the kitchen area, add and relocate pendant in the 2nd floor closet and provide hangers where noted on the approved job site drawings 10/3/2002 2:56:10 PM
FIR02-00239 INSP-Final Inspection10/2/200210/3/200210/3/2002 12:00:00 AMAPART
A temporary occupancy was given on the fire alarm system per Dave Miller's approval until the additional strobes are added in the rooms and the existing horn/strobes in the rooms are relocated 10/3/2002 8:21:48 AM
FIR02-00128 INSP-Final Inspection10/3/200210/3/200210/3/2002 12:00:00 AMAPASS
fire sprinkler system finaled
BLD01-02828 FIRE-Final Inspection10/3/200210/3/200210/3/2002 12:00:00 AMAPART
A temporary occupancy was given on the fire alarm system per Dave Miller's approval until the additional strobes are added in the rooms and the existing horn/strobes in the rooms are relocated
FIR02-00364 INSP-Final Inspection10/3/200210/3/200210/3/2002 12:00:00 AMPCANC
contractor did not call for this inspection 10/3/2002 3:48:18 PM
FIR02-00354 INSP-Final Inspection10/3/200210/3/200210/3/2002 12:00:00 AMPFAIL
hangers along the tenant separation wall still need to be installed to the top of the truss 10/3/2002 12:45:45 PM
FIR02-00363 INSP-Sprinkler Rough-in/Hydro10/3/200210/3/200210/3/2002 12:00:00 AMPPART
First floor sprinklers are OK to cover. Second floor still needs cover inspection. Notified the contractor to double check the distance the sidewall sprinkler heads in the garage are from the ceiling and to provide insulation on vertical risers along garage wall 10/3/2002 2:00:56 PM
BLD02-01618 FIRE-Final Inspection10/3/200210/3/200210/3/2002 12:00:00 AMPFAIL
submitt sprinkler drawings as per the fire dept plan review comments for the possible high pile storage and the rack sprinklers 10/3/2002 3:54:43 PM