Inspections for the day of: Wednesday, October 3, 2007.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04666 Final10/3/200710/3/200710/3/2007 3:45:42 PMPFAIL
Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson met contractor, left correction notice, nec 312.5 all conductors entering enclosure shall have abrasion protection, 250.24 grounding shall be isolated from grounded conductor, renove bonding screw, 110.26(A) shall provide workspace for receptacle, cover shall open, told contractor can't final until they call for permanent service, this 2nd day in a row this was called for final
ELE07-01468 Permanent Service10/3/200710/3/200710/3/2007 3:02:05 PMPCANC
patrick Phone #: ###-#### wrong inspection request, owner hired contractor to change service, see ele07-03419
ELE07-03419 Permanent Service10/3/200710/3/200710/3/2007 3:02:04 PMPPASS
p/s u/g rec ok
ELE07-02963 Electrical Rough-In10/2/200710/3/200710/3/2007 1:55:38 PMPPART
Wall Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton kitchen hoo d walls and bath walls only ok to cover anop, looked at columns and ok too
ELE07-03403 Electrical Rough-In10/3/200710/3/200710/3/2007 1:52:40 PMPPASS
Scheduled by a contractor via Hello! on 10/3/2007 at 7:57:41 AM. Contact: ###-####. soffits only ok to cover
ELE07-03407 Electrical Rough-In10/3/200710/3/200710/3/2007 1:04:37 PMPPASS
brandon Note: groundwork Phone #: ###-#### u/g house to garage only, both sides ok
ELE07-03409 Electrical Rough-In10/3/200710/3/200710/3/2007 1:02:35 PMPPASS
brandon Note: groundwork Phone #: ###-#### u/g house to garage only, both sides ok
ELE07-03348 Rough-In Permanent Service10/3/200710/3/200710/3/2007 12:59:52 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Brandon Blackham correction made, u/g house to garage ok, both sides, ric ok, both sides, p/s u/g n ok 1 unit only (west side)
ELE07-03410 Rough-In Permanent Service10/3/200710/3/200710/3/2007 12:57:48 PMPCANC
brandon - underground Phone #: ###-#### wrong type request, see ri
ELE07-03410 Electrical Rough-In10/3/200710/3/200710/3/2007 12:57:15 PMPPASS
brandon - underground Phone #: ###-#### ri u/g house to garage only ok, both sides
ELE07-03097 Final10/3/200710/3/200710/3/2007 12:15:22 PMPNR
jason Phone #: ###-#### called, left card, nobody home, looked in window, receptacles and switch not installed, fee due
ELE06-00482 Final10/2/200710/3/200710/3/2007 11:27:46 AMAPASS
tom Note: call for lockbox Phone #: ###-#### ok to final, no card to sign
ELE07-01198 Electrical Rough-In10/1/200710/3/200710/3/2007 10:28:02 AMAPASS
scott - re-inspection Phone #: ###-#### corrections made, ric ok garage and great room
ELE07-03361 Electrical Rough-In10/3/200710/3/200710/3/2007 9:56:57 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Bob Glenn u/g house to garage ok to cover, ric ok house and garage, note no power to shed with 3 walls
ELE07-03405 Electrical Rough-In10/2/200710/3/200710/3/2007 9:19:21 AMAPASS
DUSTIN nOTE; PLEASE CALL 1/2 HR PRIOR TO INSPECTION TO GET IN Phone #: ###-#### ok to cover kitchen and dining area
ELE07-03114 Electrical Rough-In10/2/200710/3/200710/3/2007 8:59:35 AMAFAIL
Ceiling. Restaurant opens at 8:30 Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton called contractor, left corr notice, BCC ALLceiling tiles shall be removed for inspection, no low voltage shall be on grid
ELE07-03394 Electrical Rough-In10/2/200710/3/200710/3/2007 8:29:38 AMAPASS
Scheduled by a contractor via Hello! on 10/2/2007 at 8:35:13 PM. Contact: ###-####. walls only ok to cover, corrections made
ELE07-03144 Electrical Rough-In10/3/200710/3/200710/3/2007 8:06:20 AMAPASS
Scheduled by a contractor via Hello! on 10/3/2007 at 6:39:57 AM. Contact: ###-####. met elect, ok to cover ceiling only