Inspections for the day of: Monday, October 3, 2011.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00062 FIR-Aging Inspection10/3/201110/3/201110/6/2011 8:40:42 AM NR
I forwarded this permit number and status to scott for further action.
FIR11-00379 INSP-Final Inspection9/30/201110/3/201110/3/2011 3:35:45 PMPPASS
Permit finaled. The EOL was 2/10 of a volt outside the allowed minimum voltage. Since the panel is going to be replaced in two days it was agreed to allow this temporary condition.
FIR11-00529 INSP-Final Inspection10/3/201110/3/201110/3/2011 2:33:10 PMPPASS
Permit finaled
BLD11-01889 FIRE-Final Inspection10/3/201110/3/201110/3/2011 2:32:42 PMPCANC
This permit called in by mistake by the sprinkler contractor.
BLD10-02666 FIRE-Conference9/30/201110/3/201110/3/2011 2:31:40 PMADONE
The insulation filling the combustible concealed spaces has been verified.
FIR11-00525 INSP-Final Inspection10/3/201110/3/201110/3/2011 1:55:11 PMPFAIL
The overspaced pendant has been corrected. Will be able to final when the ceiling tile is installed.
BLD11-01961 FIRE-Final Inspection10/3/201110/3/201110/3/2011 1:43:18 PMPPASS
life safety passed
BLD11-01888 FIRE-Final Inspection9/30/201110/3/201110/3/2011 9:30:43 AMAPASS
life safety passed
BLD11-01959 FIRE-Final Inspection9/30/201110/3/201110/3/2011 9:30:19 AMAFAIL
Need the ceiling tile installed and the project related fire sprinkler permit finaled. All other items are ok.
FIR11-00495 INSP-Final Inspection9/30/201110/3/201110/3/2011 9:12:21 AMACANC
A new corridor wall marked "temporary" on the city approved building plans is going to be more of a permanent wall. Sprinkler protection will need to be added on the west side.
FIR11-00436 INSP-Sprinkler Rough-in9/30/201110/3/201110/3/2011 9:10:01 AMAPART
See the city approved plans for the office area marked in red where the sprinkler piping is ok to cover. The "lab" piping was requested for cover but the upright protection for the combustible concealed space above the ceiling has been removed. Uprights will need to be installed prior to an approval for cover given.
FIR11-00228 INSP-Final Inspection10/3/201110/3/201110/3/2011 12:00:00 AMPCANC
Overbooked.

Rod or Brian #: ###-####
BLD09-00832 FIRE-Final Inspection10/3/201110/3/201110/3/2011 12:00:00 AMPCANC
Jesse Phone #: ###-####