Inspections for the day of: Thursday, October 3, 2013.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00340 INSP-Sprinkler Rough-in10/3/201310/3/201310/3/2013 3:41:37 PMPCANC
I noted that the FDC was not located on the street side of the building. So Mike wanted to just reschedule for tomorrow.
FIR13-00441 INSP-Sprinkler Rough-in10/2/201310/3/201310/3/2013 3:36:34 PMPFAIL
Todays inspection was only for the mezzanine/office area. Resubmit plans showing the pipe routing changes to the office/mezzanine area, the use of cpvc piping and flat face bushings. No piping to be covered at this time. Also noted sprinkler main piping hangers utilizing the bottom chord of the z purlins which will need approval.
FIR13-00506 INSP-Sprinkler Rough-in10/3/201310/3/201310/3/2013 3:26:17 PMPPASS
The two pendants located in the showers are ok to cover.
BLD13-02527 FIRE-Final Inspection10/2/201310/3/201310/3/2013 2:52:26 PMAFAIL
Repair the exit sign and provide automatic release via smoke detectors for the door in the one hour rated wall between storage and retail areas.
FIR13-00512 INSP-Final Inspection10/3/201310/3/201310/3/2013 12:41:48 PMPPASS
permit finaled
BLD13-02661 FIRE-Final Inspection10/3/201310/3/201310/3/2013 11:39:23 AMPPASS
life safety passed
FIR13-00453 INSP-Final Inspection10/2/201310/3/201310/3/2013 10:58:30 AMAPASS
IBR cover inspection passed
BLD11-00519 FIRE-Final Inspection10/2/201310/3/201310/3/2013 9:16:17 AMAPASS
life safety passed
BLD13-02661 FIRE-Final Inspection10/2/201310/3/201310/3/2013 8:41:08 AMAFAIL
Provide annual inspection for the fire extinguishers, provide one in the storage area, and provide approved hardware on the three exit doors as discussed