ELE12-01987
| ELE-Aging Inspection | 10/3/2014 | 10/3/2014 | 10/6/2014 3:01:43 PM | | DONE |
|
|
Spoke to homeowner who still intends on doing service change when finances allow. Still under construction
|
ELE14-00037
| Final | 10/3/2014 | 10/3/2014 | 10/3/2014 3:30:54 PM | P | FAIL |
|
|
Lock box is 4888, thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Checked up interior, ok, open box on back fireplace on main level shall be safed off and covered. Seperate permit required for basement appartment as per notes from 7-24-14 inspection by Daryl DeGrange. 314.25 Covers and Canopies. In completed installations, each box shall have a cover, Checked up interior, ok, open box on back fireplace on main level shall be safed off and covered.
|
ELE14-02754
| Electrical Rough-In | 10/3/2014 | 10/3/2014 | 10/3/2014 2:37:21 PM | P | PASS |
|
|
Steve Phone #: ###-#### Front room addition rough in ok cover
|
ELE14-02732
| Final | 10/3/2014 | 10/3/2014 | 10/3/2014 1:55:24 PM | P | PASS |
|
|
Tied conduit into panel. HP is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Permit to install undrground for future wiring only. Final ok
|
ELE14-02739
| Conference | 10/2/2014 | 10/3/2014 | 10/3/2014 1:31:29 PM | P | DONE |
|
|
Please call ahead for access/10mins - Jerry Phone #: ###-#### Discussed box fill, min required receptical outlets, GFCI protection of kitchen and bath, min. number of circuits serving kit counter and bathrooms. 6' rule for habitable rooms
|
ELE14-02737
| Temporary Service | 10/2/2014 | 10/3/2014 | 10/3/2014 12:33:19 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Paul Young t/s o/h n ok
|
ELE14-02171
| Electrical Rough-In | 9/30/2014 | 10/3/2014 | 10/3/2014 11:36:47 AM | A | PASS |
|
|
Timothy Phone #: ###-#### Shed rough in ok cover
|
ELE14-02171
| Permanent Service | 10/3/2014 | 10/3/2014 | 10/3/2014 11:33:21 AM | P | PASS |
|
|
Timothy Phone #: ###-#### p/s o/h n ok
|
ELE14-02758
| Permanent Service | 10/3/2014 | 10/3/2014 | 10/3/2014 11:20:38 AM | P | CANC |
|
|
RE ENERGIZE, POWER OFF OVER A YEAR. Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
|
ELE14-02699
| Final | 10/2/2014 | 10/3/2014 | 10/3/2014 10:27:56 AM | A | FAIL |
|
|
If you have any questions, please call the office. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Service change complete however open wiring in kitchen area. Due to this open wiring permit to remain open until permit is created to cover any interior wiring needed. 406.4 General Installation Requirements (2) Non–Grounding-Type Receptacles. Where attachment to an equipment grounding conductor does not exist in the receptacle enclosure, the installation shall comply with (D)(2)(a), (D)(2)(b), or (D)(2)(c). (a) A non–grounding-type receptacle(s) shall be permitted to be replaced with another non–grounding-type receptacle( s). (b) A non–grounding-type receptacle(s) shall be permitted to be replaced with a ground-fault circuit interruptertype of receptacle(s). These receptacles shall be marked “No Equipment Ground.” An equipment grounding conductor shall not be connected from the ground-fault circuitinterrupter- type receptacle to any outlet supplied from the ground-fault circuit-interrupter receptacle. (c) A non–grounding-type receptacle(s) shall be permitted to be replaced with a grounding-type receptacle(s) where supplied through a ground-fault circuit interrupter. Grounding-type receptacles supplied through the groundfault circuit interrupter shall be marked “GFCI Protected” and “No Equipment Ground.” An equipment grounding conductor shall not be connected between the groundingtype receptacles. (3) Ground-Fault Circuit Interrupters. Ground-fault
|
ELE14-02635
| Rough-In Permanent Service | 10/3/2014 | 10/3/2014 | 10/3/2014 9:41:51 AM | P | CANC |
|
|
Early as possible - Tom Phone #: ###-#### needed rough in only
|
ELE14-02635
| Electrical Rough-In | 10/3/2014 | 10/3/2014 | 10/3/2014 9:41:51 AM | P | PASS |
|
|
Early as possible - Tom Phone #: ###-#### Bthroom shower stall only rough in ok cover
|
ELE14-02700
| Electrical Rough-In | 10/1/2014 | 10/3/2014 | 10/3/2014 9:18:06 AM | A | PASS |
|
|
BREAK ROOM WALLS Phone #: ###-#### Inspection requested via web by Kerri Hamilton Bath walls only rough in ok cover
|
ELE14-02706
| Electrical Rough-In | 10/2/2014 | 10/3/2014 | 10/3/2014 8:58:11 AM | A | PASS |
|
|
This inspection will be a Office ; Wall rough in inspection. Contact is Kyle Little ###-####. Kyle will be on site. Thank you and have a great day! Phone #: ###-#### Inspection requested via web by Laura Longshaw Front office and dividing wall rough in ok cover
|