Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-01987 ELE-Aging Inspection10/3/201410/3/201410/6/2014 3:01:43 PM DONE
Spoke to homeowner who still intends on doing service change when finances allow. Still under construction
ELE14-00037 Final10/3/201410/3/201410/3/2014 3:30:54 PMPFAIL
Lock box is 4888, thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Checked up interior, ok, open box on back fireplace on main level shall be safed off and covered. Seperate permit required for basement appartment as per notes from 7-24-14 inspection by Daryl DeGrange.
314.25 Covers and Canopies. In completed installations,
each box shall have a cover, Checked up interior, ok, open box on back fireplace on main level shall be safed off and covered.
ELE14-02754 Electrical Rough-In10/3/201410/3/201410/3/2014 2:37:21 PMPPASS
Steve Phone #: ###-#### Front room addition rough in ok cover
ELE14-02732 Final10/3/201410/3/201410/3/2014 1:55:24 PMPPASS
Tied conduit into panel. HP is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen Permit to install undrground for future wiring only. Final ok
ELE14-02739 Conference10/2/201410/3/201410/3/2014 1:31:29 PMPDONE
Please call ahead for access/10mins - Jerry Phone #: ###-#### Discussed box fill, min required receptical outlets, GFCI protection of kitchen and bath, min. number of circuits serving kit counter and bathrooms. 6' rule for habitable rooms
ELE14-02737 Temporary Service10/2/201410/3/201410/3/2014 12:33:19 PMPPASS
Phone #: ###-#### Inspection requested via web by Paul Young t/s o/h n ok
ELE14-02171 Electrical Rough-In9/30/201410/3/201410/3/2014 11:36:47 AMAPASS
Timothy Phone #: ###-#### Shed rough in ok cover
ELE14-02171 Permanent Service10/3/201410/3/201410/3/2014 11:33:21 AMPPASS
Timothy Phone #: ###-#### p/s o/h n ok
ELE14-02758 Permanent Service10/3/201410/3/201410/3/2014 11:20:38 AMPCANC
RE ENERGIZE, POWER OFF OVER A YEAR. Phone #: ###-#### >> Inspection requested via web by Eric Schroeder Inspection cancelled from web by: Eric Schroeder
ELE14-02699 Final10/2/201410/3/201410/3/2014 10:27:56 AMAFAIL
If you have any questions, please call the office. Thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Service change complete however open wiring in kitchen area. Due to this open wiring permit to remain open until permit is created to cover any interior wiring needed.
406.4 General Installation Requirements (2) Non–Grounding-Type Receptacles. Where attachment
to an equipment grounding conductor does not exist
in the receptacle enclosure, the installation shall comply
with (D)(2)(a), (D)(2)(b), or (D)(2)(c).
(a) A non–grounding-type receptacle(s) shall be permitted
to be replaced with another non–grounding-type receptacle(
s).
(b) A non–grounding-type receptacle(s) shall be permitted
to be replaced with a ground-fault circuit interruptertype
of receptacle(s). These receptacles shall be marked
“No Equipment Ground.” An equipment grounding conductor
shall not be connected from the ground-fault circuitinterrupter-
type receptacle to any outlet supplied from the
ground-fault circuit-interrupter receptacle.
(c) A non–grounding-type receptacle(s) shall be permitted
to be replaced with a grounding-type receptacle(s)
where supplied through a ground-fault circuit interrupter.
Grounding-type receptacles supplied through the groundfault
circuit interrupter shall be marked “GFCI Protected”
and “No Equipment Ground.” An equipment grounding
conductor shall not be connected between the groundingtype
receptacles.
(3) Ground-Fault Circuit Interrupters. Ground-fault
ELE14-02635 Rough-In Permanent Service10/3/201410/3/201410/3/2014 9:41:51 AMPCANC
Early as possible - Tom Phone #: ###-#### needed rough in only
ELE14-02635 Electrical Rough-In10/3/201410/3/201410/3/2014 9:41:51 AMPPASS
Early as possible - Tom Phone #: ###-#### Bthroom shower stall only rough in ok cover
ELE14-02700 Electrical Rough-In10/1/201410/3/201410/3/2014 9:18:06 AMAPASS
BREAK ROOM WALLS Phone #: ###-#### Inspection requested via web by Kerri Hamilton Bath walls only rough in ok cover
ELE14-02706 Electrical Rough-In10/2/201410/3/201410/3/2014 8:58:11 AMAPASS
This inspection will be a Office ; Wall rough in inspection. Contact is Kyle Little ###-####. Kyle will be on site. Thank you and have a great day! Phone #: ###-#### Inspection requested via web by Laura Longshaw Front office and dividing wall rough in ok cover