Inspections for the day of: Friday, October 3, 2014.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00394 INSP-Final Inspection10/2/201410/3/201410/6/2014 5:53:30 PMPDEFR
FIR14-00486 INSP-Final Inspection10/2/201410/3/201410/3/2014 4:16:59 PMPDEFR
FIR14-00712 INSP-Sprinkler Rough-in10/3/201410/3/201410/3/2014 4:16:25 PMPPART
UG fire supply line approved for bury.
BLD14-01046 FIRE-Final Inspection10/2/201410/3/201410/3/2014 3:39:41 PMPPASS
Life safety inspection passed. No signature card available on site.
FIR14-00344 INSP-Sprinkler Rough-in10/2/201410/3/201410/3/2014 2:56:29 PMAPART
Rough-in inspection for portions of building B 4th floor completed to date- Items noted include; three overspaced CC2 heads, relocate one CC2 away from truss web, SW heads and supply piping are not yet installed, 2" CPVC main at the corridor and extending into one unit is not installed, two additional branchlines with CC2 heads have been installed due to draft stops and are not included on plans. The trash room, elevator lobby, data, and housekeeping areas are not piped at this time. Refer to plans for annotations.
BLD14-02750 FIRE-Final Inspection10/3/201410/3/201410/3/2014 2:47:40 PMPPASS
Scope of permit work passed life safety inspection.
FIR14-00665 INSP-Final Inspection10/2/201410/3/201410/3/2014 1:20:52 PMAPASS
Fire alarm permit finaled. Inspection passed. Points map at panel revised to include new the new modular classroom and initiation devices.
FIR14-00670 INSP-Final Inspection9/30/201410/3/201410/3/2014 1:16:47 PMAPASS
Scope of work completed and passed site inspection. Fire alarm permit finaled.
FIR14-00401 INSP-Final Inspection10/2/201410/3/201410/3/2014 1:15:28 PMAPASS
Fire alarm work passed functional testing. Contractor to install lock and label breaker as discussed.