ELE15-01348
| Electrical Rough-In | 10/3/2016 | 10/3/2016 | 10/3/2016 2:41:21 PM | P | PASS |
|
|
overhead and walls rough in at ramp. call Frank Phone #: ###-#### Inspection requested via web by Brandon Robinson Wall near stair 2 not framed yet. Rest of ramp walls and ceiling rough in ok cover
|
ELE16-01838
| Final | 10/3/2016 | 10/3/2016 | 10/3/2016 2:41:06 PM | A | FAIL |
|
|
Re-inspection Level 2,3, 4, 5, 6 Stack 1,2,3,4 Phone #: ###-#### Inspection requested via web by Tom Betty Level 2 stair 1 lighting in still need paint. Support blind cables up out of reach. Furniture covers still loose on low voltage side. Skipped level 3. Level 4 loose low volt covers. Furniture missing, whips in with open ends. Elevator vestibule low volt supported by EMT. Level 5 furniture covers loose on low voltage side. Open neutral 51A 28, 30, 32. Stack 1 lab to remain unfinished. Furniture whips in furniture missing. Level 6 same as level 5. 62C 8 missing receptacle. Uppper ladder rack bond needed. Level 7 not ready 250.8(A)(6)- Bonding of cable trays and ladder racks connections completed with lag type self tapping screws. Machine type thread required.
|