FIR16-00473
| INSP-Sprinkler Rough-in/Hydro | 10/3/2016 | 10/3/2016 | 10/3/2016 2:25:15 PM | P | PASS |
|
|
200 psi hydrostatic test for underground supply complete.
|
BLD16-02946
| FIRE-Final Inspection | 10/3/2016 | 10/3/2016 | 10/3/2016 2:23:58 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in common area's, superintendent provided detail for door hardware that will be installed on exterior door. Final life fire safety inspection passed/complete.
|
FIR15-00198
| INSP-Alarm Testing | 10/3/2016 | 10/3/2016 | 10/3/2016 12:45:43 PM | P | CANC |
|
|
Call for access Phone #: 2089411846 >> Inspection requested via mobile web by Brian A Inspection cancelled via mobile web on Monday, October 03, 2016.
|
FIR15-00574
| INSP-Final Inspection | 9/30/2016 | 10/3/2016 | 10/3/2016 11:29:02 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete.
|
FIR15-00561
| INSP-Final Inspection | 10/3/2016 | 10/3/2016 | 10/3/2016 11:28:38 AM | P | PASS |
|
|
Final fire sprinkler inspection passed/complete.
|
FIR16-00244
| INSP-Sprinkler Rough-in/Hydro | 9/30/2016 | 10/3/2016 | 10/3/2016 11:27:56 AM | A | PART |
|
|
200psi hydrostatic test for all overhead fire sprinkler systems associated with this permit complete. 24 hour air test started at 11:00 am @ 40psi.
|