ELE13-00163
| ELE-Aging Inspection | 10/3/2017 | 10/3/2017 | 10/3/2017 1:47:35 PM | | FAIL |
|
|
have tried to make contact twice...contractor needs to get access and schedule final
|
ELE17-03214
| Electrical Rough-In | 10/2/2017 | 10/3/2017 | 10/3/2017 1:41:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Jonathan Poot...rough ok to cover
|
ELE17-02598
| Electrical Rough-In | 10/2/2017 | 10/3/2017 | 10/3/2017 1:13:13 PM | P | PASS |
|
|
call 20 min before to meet // Michael Phone #: ###-####...ok to cover
|
ELE17-02391
| Final | 10/3/2017 | 10/3/2017 | 10/3/2017 12:50:06 PM | P | PASS |
|
|
7373 Phone #: ###-#### Inspection requested via web by Heath Thomas...
ok to final
|
ELE17-03313
| Permanent Service | 10/2/2017 | 10/3/2017 | 10/3/2017 10:55:22 AM | A | FAIL |
|
|
Joe Phone #: ###-####...nec 250.56 second ground rod needed 6' apart from first ground rod, ground rod shall be installed 8' into ground at finish grade, open hole in disconnect needs sealed
|
ELE16-03793
| Electrical Rough-In | 10/2/2017 | 10/3/2017 | 10/3/2017 10:14:21 AM | A | PASS |
|
|
CONTACT: JEREMY THORNOCK Phone #: ###-#### Inspection requested via web by Deb Gooden...ok to cover walls and hard lids..full building 300
|
ELE17-03273
| Electrical Rough-In | 10/2/2017 | 10/3/2017 | 10/3/2017 9:02:11 AM | A | PASS |
|
|
underground conduit to be covered with concrete Phone #: ###-#### Inspection requested via web by ron spen cer...ok to cover feed to shop..shall be covered in 4" minimum concrete
|
ELE17-02231
| Final | 10/2/2017 | 10/3/2017 | 10/3/2017 8:21:14 AM | A | PASS |
|
|
Justin Hamby Phone #: ###-#### Inspection requested via web by Laurie Hoelscher...UL listing and disconnect...ok to final
|
ELE17-02988
| Electrical Rough-In | 9/28/2017 | 10/3/2017 | 10/2/2017 3:45:24 PM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Kurtis Boller...
inspection done 10/2/17 PM
|
ELE17-03276
| Rough-In Permanent Service | 10/2/2017 | 10/3/2017 | 10/2/2017 2:02:15 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Dan Rohl...rough ok to cover....p/s u/g new ok
|
ELE17-02527
| Final | 10/2/2017 | 10/3/2017 | 10/2/2017 12:33:51 PM | A | CANC |
|
|
Garage Code 1001E Phone #: ###-#### Inspection requested via web by Alan Lusk.. scheduled twice
|