Inspections for the day of: Thursday, October 3, 2019.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-02727 Final10/3/201910/3/201910/3/2019 3:09:45 PMPPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
ELE14-01181 ELE-Aging Inspection10/3/201910/3/201910/3/2019 2:14:06 PM FAIL
No corrections made No final scheduled
ELE19-01403 Electrical Rough-In10/2/201910/3/201910/3/2019 2:13:39 PMPPASS
Cover inspection for the NWPG for level 1 slab 3
Contact electrician on site - John Mittleider
Thank you, Phone #: ###-#### Inspection requested via web by Cathy Duchek Level 1 Slab 3, Ok to cover
ELE19-03131 Permanent Service10/3/201910/3/201910/3/2019 1:16:12 PMPPASS
Kim RME ###-####. Rescheduled from10/2 upon Kim's request. Service is existing. Bumped to 600A from 400A. CT meter not onsite at time of service inspection p/s u/g rec ok
ELE19-03692 Permanent Service10/2/201910/3/201910/3/2019 12:56:43 PMPPASS
call with questions Phone #: ###-#### Inspection requested via web by Garrett Collins Need to check sub panel at final for seperation of grounds. p/s u/g n ok
ELE19-03568 Electrical Rough-In10/3/201910/3/201910/3/2019 12:33:19 PMPPASS
underground // jose Phone #: ###-#### Underground from main service to back of Stage ok to cover
ELE18-04218 Conference10/2/201910/3/201910/3/2019 11:33:12 AMADONE
Please call Bill for a conference call Phone #: ###-#### Inspection requested via web by Rhonda Yoast Talked about when to schedule final. Need porwer restored after other contractor finishes up sizing service.
ELE19-03131 Permanent Service10/2/201910/3/201910/3/2019 10:32:39 AMANR
Kim RME ###-####. Rescheduled from10/2 upon Kim's request. Not ready still landing feeders and grounding electrode conductor
ELE19-03740 Rough-In Permanent Service10/3/201910/3/201910/3/2019 10:31:09 AMAPASS
Phone #: ###-#### Inspection requested via web by Therrin Robertson Corrections made rough in ok p/s u/g n ok
ELE19-02932 Rough-In Permanent Service10/2/201910/3/201910/3/2019 9:59:07 AMAPASS
Phone #: ###-#### Inspection requested via web by kevin blackmon rough in ok p/s u/g n ok
ELE19-03668 Rough-In Permanent Service10/2/201910/3/201910/3/2019 9:04:06 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn correction made p/s u/g n ok