Inspections for the day of: Thursday, October 3, 2019.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03096 Rough-in10/3/201910/3/201910/3/2019 4:34:55 PMPFAIL
2nd ; 3rd floor exhaust fans, 4th floor radiant dampers. Please call Bryan at least 30 min prior to inspection, thank you! Phone #: ###-#### Inspection requested via web by Rhonda Marcum
- exhaust fans are not installed per prints on 2nd, 3rd and 4th floor
MEC19-03744 Final10/2/201910/3/201910/3/2019 4:16:24 PMPPASS
Please call home owner at ###-#### to confirm she is home and able to provide access. Phone #: ###-#### Inspection requested via web by terry Warden
- final ok
MEC19-04400 Final10/3/201910/3/201910/3/2019 2:54:04 PMPPASS
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek
- furnace only co ok
MEC19-04400 Pressure Test10/3/201910/3/201910/3/2019 2:53:48 PMPPASS
Phone #: ###-#### Inspection requested via web by Floyd Floyd Peek
- 5lb flue pressure test ok
MEC19-04351 Final10/2/201910/3/201910/3/2019 2:11:52 PMPFAIL
Please call realtor Jenny at Lysi Bishop at ###-#### and she will meet you for access Phone #: ###-#### Inspection requested via web by Justin Osterhout
- furnace PVC flue needs 6" clearances from single wall water heater flue
MEC19-04347 Final10/1/201910/3/201910/3/2019 1:47:03 PMPNR
field super : chad Robertson Phone #: ###-#### Inspection requested via web by Lisa Whitney
MEC19-00986 Final10/2/201910/3/201910/3/2019 1:35:21 PMPPASS
Please call Brian at ###-#### 30 min prior so he can meet the inspector on site to let him in. Phone #: ###-#### Inspection requested via web by Ashley Shoecraft
- final ok
MEC19-04367 Final10/2/201910/3/201910/3/2019 1:27:09 PMPPASS
Dan ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks
- A/C coil co ok
MEC19-04097 Rough-in10/2/201910/3/201910/3/2019 12:13:18 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves
- need stamped man J onsite
- return air for both furnaces not per prints
- fresh air needs to tap off furnace return plenum not return can
- water heater 5lb flue fail
MEC19-04097 Pressure Test10/2/201910/3/201910/3/2019 12:10:44 PMPFAIL
Phone #: ###-#### Inspection requested via web by Gary Reeves
- 5lb flue for furnace ok
- 20lb and 60lb gas pressure test ok
- tagged meter location
- water heater 5lb flue test fail under 5lb
MEC19-03819 Final10/3/201910/3/201910/3/2019 12:09:26 PMPFAIL
Call Emma in route to inspection ###-####--she may not be home but corrections are visible from outside of home. Phone #: ###-#### Inspection requested via web by Justin Osterhout
- still need to see an electrical permit pulled for ductless system
MEC19-02782 Final10/3/201910/3/201910/3/2019 11:43:44 AMPPASS
Michael Phone #: ###-####
- final ok
MEC19-04112 Final10/2/201910/3/201910/3/2019 11:42:47 AMPPASS
Electrical permit has been pulled for the A/C install. ELEC19-03736
Please call Home owner at ###-#### if you need access inside house. Phone #: ###-#### Inspection requested via web by terry Warden
- final ok
MEC19-01963 Final10/2/201910/3/201910/3/2019 10:47:43 AMAPASS
Phone #: ###-#### Inspection requested via web by Sheldon Lebow

- fireplace final ok
MEC19-02186 Final10/1/201910/3/201910/3/2019 10:31:09 AMAPASS
access code for entry should be 4224 or 2529 Phone #: ###-#### Inspection requested via web by Angie Maguire
- final ok
MEC19-04389 Rough-in10/2/201910/3/201910/3/2019 10:05:52 AMAPASS
Phone #: ###-#### Inspection requested via web by Sheldon Lebow
- fireplace R/I ok
MEC19-04385 Final10/2/201910/3/201910/3/2019 9:34:34 AMAFAIL
Replace existing furnace with a new furnace. Added a air conditioner. Phone #: ###-#### Inspection requested via web by jeremy wanders
- need locking caps on A/C service ports
- need to seal line set penetration
- electrical wiring to furnace is touching b vent and needs terminated properly at furnace
-secondary drain needs a wet switch installed
- vent piping from furnace needs slope with out dips and sags
- natural draft needs to connect at highest point in common vent above fan assist appliance
MEC19-02272 Final10/1/201910/3/201910/3/2019 8:46:35 AMAPASS
please call john 30 min prior to arriving so he can meet you onsite
thanks
Phone #: ###-#### Inspection requested via web by Nicholas Paige
- final ok
signed occ card
- talked with John about pulling a seperate mech permit for the shell gas piping and two unit heaters