FIR01-00421
| INSP-Sprinkler Rough-in/Hydro | 10/29/2001 | 10/30/2001 | 10/30/2001 12:00:00 AM | A | PASS |
|
|
Aboveground hydro test OK 10/29/2001 4:00:31 PM
|
FIR01-00421
| INSP-Final Inspection | 10/29/2001 | 10/30/2001 | 10/30/2001 12:00:00 AM | A | NR |
|
|
Not ready for final. Alarm system and outside canopy to be finished. 10/29/2001 4:00:12 PM
|
FIR01-00370
| INSP-Sprinkler Rough-in/Hydro | 10/29/2001 | 10/30/2001 | 10/30/2001 12:00:00 AM | A | PASS |
|
|
Above ground hydro test OK. FDC to be hydro yet. 10/30/2001 12:47:55 PM
|
BLD01-01045
| FIRE-Final Inspection | 10/29/2001 | 10/30/2001 | 10/30/2001 12:00:00 AM | A | FAIL |
|
|
1 hour wall needs to be completed and duct detector is to be installed on mech unit in basement 10/31/2001 9:14:50 AM
|
BLD01-02555
| FIRE-Final Inspection | 10/30/2001 | 10/30/2001 | 10/30/2001 12:00:00 AM | P | PART |
|
|
Fire sprinkler system is OK and signed off. Smoke detector and fire damper operation on the fire alarm system needs to be tested. 10/31/2001 9:17:05 AM
|
MIS01-00213
| FIR-Final | 10/29/2001 | 10/30/2001 | 10/30/2001 12:00:00 AM | P | FAIL |
|
|
Left correction notice on requirements for doors, exit lights, emergency lights and fire extinguishers. 10/31/2001 9:15:51 AM
|
FIR01-00505
| INSP-Sprinkler Rough-in/Hydro | 10/29/2001 | 10/30/2001 | 10/30/2001 12:00:00 AM | P | PASS |
|
|
Left correction notice. Install hose station outlet, pendents overspace in corr. 110, pendents not installed in restroom and computer room, taped heads in restroom, hangers missing, FDC leaking, install alarm bell, verify test orfice matches head, provide letter stating heads are installed in canopies. 10/31/2001 9:19:52 AM
|