ELE05-02730
| ELE-Aging Inspection | 10/30/2006 | 10/30/2006 | 11/1/2006 6:49:49 AM | | PART |
|
|
wsuc
|
ELE06-02800
| ELE-Aging Inspection | 10/30/2006 | 10/30/2006 | 11/1/2006 6:49:10 AM | | PART |
|
|
wsuc
|
ELE06-03701
| Permanent Service | 10/30/2006 | 10/30/2006 | 10/30/2006 4:30:31 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/30/2006 at 9:23:43 AM. Contact: ###-####. p/s u/g new ok
|
ELE06-03958
| Electrical Rough-In | 10/27/2006 | 10/30/2006 | 10/30/2006 3:37:51 PM | P | PART |
|
|
Reinspection for (1) Ceiling cover in west dining area. (2) Entry to kitchen.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen walls and ceiling in west din. area only
|
ELE06-03484
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 3:00:05 PM | P | FAIL |
|
|
Final Inspection Quiznos 10697 Ustick Rd Boise Nick Avery ###-####; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson corr called 250.104(A)(1) bond hot and cold , 300.7 seal raceways entering freezer and cooler inside of raceways, 210.8(B)(2) gfci all recepts in front ,and back areas of kit, B C C ceilings covered before inspection electrical contr told general not to cover he did it anyway, remove tiles
|
ELE06-03984
| Electrical Rough-In | 10/30/2006 | 10/30/2006 | 10/30/2006 2:26:14 PM | P | PART |
|
|
Scheduled by a contractor via Hello! Note: for uifer and trench inspection on 10/30/2006 at 11:24:26 AM. Contact: ###-####. u/g ok, electrode ok for concrete cover
|
ELE06-03983
| Electrical Rough-In | 10/30/2006 | 10/30/2006 | 10/30/2006 2:25:16 PM | P | PART |
|
|
Scheduled by a contractor via Hello! Note: for uifer and trench inspection on 10/30/2006 at 11:22:43 AM. Contact: ###-####. u/g ok and electrode ok for concrete cover
|
ELE06-03976
| Rough-In Permanent Service | 10/30/2006 | 10/30/2006 | 10/30/2006 2:24:04 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/30/2006 at 11:21:34 AM. Contact: ###-####. r/i for house / office ok needs 3/0 copper for 200 amps commercial sevices met with Alan he will correct, p/s u/g new ok
|
ELE06-02505
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 1:43:20 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/30/2006 at 7:15:37 AM. Contact: ###-####. ok survey posted called, 210.70 3-4 way for stairs 408.4 panel directory sall be specific as to location and purpose of circuits
|
ELE06-03096
| Electrical Rough-In | 10/30/2006 | 10/30/2006 | 10/30/2006 12:18:10 PM | P | PART |
|
|
THIS IS FOR A UNDERGROUND INSPECTION, ANY QUESTIONS PLEASE CALL STEVE FLANNARY; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok u/g
|
ELE06-03098
| Electrical Rough-In | 10/30/2006 | 10/30/2006 | 10/30/2006 12:17:45 PM | P | PART |
|
|
THIS IS FOR AN UNDERGROUND INSPECTION, ANY QUESTIONS PLEASE CALL STEVE FLANNERY; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok u/g
|
ELE06-03097
| Electrical Rough-In | 10/30/2006 | 10/30/2006 | 10/30/2006 12:17:19 PM | P | PART |
|
|
THIS IS FOR AN UNDERGROUNG INSPECTION, ANY QUESTIONS PLEASE CALL STEVE FLANNERY; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok u/g
|
ELE06-03903
| Conference | 10/30/2006 | 10/30/2006 | 10/30/2006 11:10:23 AM | A | CANC |
|
|
Scheduled by a contractor via Hello! on 10/30/2006 at 6:13:23 AM. Contact: ###-####. see added r/i
|
ELE06-03903
| Electrical Rough-In | 10/30/2006 | 10/30/2006 | 10/30/2006 11:09:49 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/30/2006 at 6:13:23 AM. Contact: ###-####. corr. calle 300.4 nail plates and 11/4", 314.16 box fill , 314.14 6" free length, 314.43 no screws alled in plastic boxes,
|
ELE06-03513
| Electrical Rough-In | 10/27/2006 | 10/30/2006 | 10/30/2006 10:40:07 AM | A | PASS |
|
|
PAUL UNDERGROUND ELECTRICAL ROOM; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy r/i for u/g to panel in elect rm ok
|
ELE06-03136
| Final | 10/27/2006 | 10/30/2006 | 10/30/2006 9:55:24 AM | A | NR |
|
|
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called corrections not made
|
ELE06-03461
| Rough-In Permanent Service | 10/27/2006 | 10/30/2006 | 10/30/2006 8:40:18 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/27/2006 at 2:55:33 PM. Contact: ###-####. called office common area shall not be wired in MNB cable shall use methods for commercial wiring
|