Inspections for the day of: Monday, October 30, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02730 ELE-Aging Inspection10/30/200610/30/200611/1/2006 6:49:49 AM PART
wsuc
ELE06-02800 ELE-Aging Inspection10/30/200610/30/200611/1/2006 6:49:10 AM PART
wsuc
ELE06-03701 Permanent Service10/30/200610/30/200610/30/2006 4:30:31 PMPPASS
Scheduled by a contractor via Hello! on 10/30/2006 at 9:23:43 AM. Contact: ###-####. p/s u/g new ok
ELE06-03958 Electrical Rough-In10/27/200610/30/200610/30/2006 3:37:51 PMPPART
Reinspection for (1) Ceiling cover in west dining area. (2) Entry to kitchen.; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen walls and ceiling in west din. area only
ELE06-03484 Final10/30/200610/30/200610/30/2006 3:00:05 PMPFAIL
Final Inspection Quiznos 10697 Ustick Rd Boise Nick Avery ###-####; Phone #: ###-#### Internet Inspection Request from: Kristopher wilson corr called 250.104(A)(1) bond hot and cold , 300.7 seal raceways entering freezer and cooler inside of raceways, 210.8(B)(2) gfci all recepts in front ,and back areas of kit, B C C ceilings covered before inspection electrical contr told general not to cover he did it anyway, remove tiles
ELE06-03984 Electrical Rough-In10/30/200610/30/200610/30/2006 2:26:14 PMPPART
Scheduled by a contractor via Hello! Note: for uifer and trench inspection on 10/30/2006 at 11:24:26 AM. Contact: ###-####. u/g ok, electrode ok for concrete cover
ELE06-03983 Electrical Rough-In10/30/200610/30/200610/30/2006 2:25:16 PMPPART
Scheduled by a contractor via Hello! Note: for uifer and trench inspection on 10/30/2006 at 11:22:43 AM. Contact: ###-####. u/g ok and electrode ok for concrete cover
ELE06-03976 Rough-In Permanent Service10/30/200610/30/200610/30/2006 2:24:04 PMPPASS
Scheduled by a contractor via Hello! on 10/30/2006 at 11:21:34 AM. Contact: ###-####. r/i for house / office ok needs 3/0 copper for 200 amps commercial sevices met with Alan he will correct, p/s u/g new ok
ELE06-02505 Final10/30/200610/30/200610/30/2006 1:43:20 PMPPASS
Scheduled by a contractor via Hello! on 10/30/2006 at 7:15:37 AM. Contact: ###-####. ok survey posted called, 210.70 3-4 way for stairs 408.4 panel directory sall be specific as to location and purpose of circuits
ELE06-03096 Electrical Rough-In10/30/200610/30/200610/30/2006 12:18:10 PMPPART
THIS IS FOR A UNDERGROUND INSPECTION, ANY QUESTIONS PLEASE CALL STEVE FLANNARY; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok u/g
ELE06-03098 Electrical Rough-In10/30/200610/30/200610/30/2006 12:17:45 PMPPART
THIS IS FOR AN UNDERGROUND INSPECTION, ANY QUESTIONS PLEASE CALL STEVE FLANNERY; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok u/g
ELE06-03097 Electrical Rough-In10/30/200610/30/200610/30/2006 12:17:19 PMPPART
THIS IS FOR AN UNDERGROUNG INSPECTION, ANY QUESTIONS PLEASE CALL STEVE FLANNERY; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok u/g
ELE06-03903 Conference10/30/200610/30/200610/30/2006 11:10:23 AMACANC
Scheduled by a contractor via Hello! on 10/30/2006 at 6:13:23 AM. Contact: ###-####. see added r/i
ELE06-03903 Electrical Rough-In10/30/200610/30/200610/30/2006 11:09:49 AMAFAIL
Scheduled by a contractor via Hello! on 10/30/2006 at 6:13:23 AM. Contact: ###-####. corr. calle 300.4 nail plates and 11/4", 314.16 box fill , 314.14 6" free length, 314.43 no screws alled in plastic boxes,
ELE06-03513 Electrical Rough-In10/27/200610/30/200610/30/2006 10:40:07 AMAPASS
PAUL UNDERGROUND ELECTRICAL ROOM; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy
r/i for u/g to panel in elect rm ok
ELE06-03136 Final10/27/200610/30/200610/30/2006 9:55:24 AMANR
Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called corrections not made
ELE06-03461 Rough-In Permanent Service10/27/200610/30/200610/30/2006 8:40:18 AMAFAIL
Scheduled by a contractor via Hello! on 10/27/2006 at 2:55:33 PM. Contact: ###-####. called office common area shall not be wired in MNB cable shall use methods for commercial wiring