MIS06-00286
| PLM-Conference | 10/27/2006 | 10/30/2006 | 10/30/2006 4:11:09 PM | A | FAIL |
|
|
###-#### a sprinkler system backflow preventor was installed at this address without a permit and inspection with unapproved material. removal and replacement of plumbing fixtures is work requiring a permit and inspection. call for a conference to go over this project with in 10 days. no additional unpermitted plumbing work is to be done.
|
PLM06-03619
| Water and/or Sewer | 10/30/2006 | 10/30/2006 | 10/30/2006 3:41:41 PM | P | CANC |
|
|
PARTIAL OOPS THIS IS FOR THE AM
|
MEC06-03431
| Rough-in | 10/27/2006 | 10/30/2006 | 10/30/2006 3:38:24 PM | P | FAIL |
|
|
marilyn Note: late afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles NEEDS 1" STANDOFF AT INSULATION SHIELD.
|
MEC06-03432
| Rough-in | 10/27/2006 | 10/30/2006 | 10/30/2006 3:37:35 PM | P | FAIL |
|
|
marilyn Note: late afternoon if possible; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles NEEDS 1" STANDOFF AT INSULATION SHIELD
|
PLM06-03676
| Plumbing Rough-in | 10/30/2006 | 10/30/2006 | 10/30/2006 3:09:05 PM | P | NR |
|
|
glenn; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
PLM06-03668
| Water and/or Sewer | 10/30/2006 | 10/30/2006 | 10/30/2006 2:54:05 PM | P | PASS |
|
|
tony; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
PLM06-03668
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 2:53:54 PM | P | PASS |
|
|
tony; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
PLM06-03669
| Water and/or Sewer | 10/30/2006 | 10/30/2006 | 10/30/2006 2:53:29 PM | P | PASS |
|
|
tony; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
PLM06-03669
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 2:53:18 PM | P | PASS |
|
|
tony; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
PLM06-03657
| Water and/or Sewer | 10/30/2006 | 10/30/2006 | 10/30/2006 2:53:00 PM | P | PASS |
|
|
dale - note: water only ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM06-03657
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 2:52:43 PM | P | PASS |
|
|
dale - note: water only ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM06-01118
| PLM-Aging Inspection | 10/30/2006 | 10/30/2006 | 10/30/2006 2:18:42 PM | | PASS |
|
|
wip
|
PLM06-03679
| Plumbing Rough-in | 10/30/2006 | 10/30/2006 | 10/30/2006 2:11:18 PM | P | PASS |
|
|
jim; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
MEC06-02909
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 1:58:29 PM | P | CANC |
|
|
Internet Inspection Request from: Becky Such r contractor said he tried to cancel this one
|
PLM06-03503
| Plumbing Rough-in | 10/30/2006 | 10/30/2006 | 10/30/2006 1:57:20 PM | P | PASS |
|
|
ina - note: as late as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith
|
PLM05-02661
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 1:30:41 PM | P | PASS |
|
|
nat; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
|
PLM06-03671
| Plumbing Rough-in | 10/30/2006 | 10/30/2006 | 10/30/2006 11:11:37 AM | P | CANC |
|
|
ina - note: as late as possible ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith Inspection cancelled from web by: Patricia Smith
|
PLM04-02719
| Final | 10/30/2006 | 10/30/2006 | 10/30/2006 9:43:19 AM | A | PASS |
|
|
ground work only final ok
|
PLM05-02661
| Final | 10/27/2006 | 10/30/2006 | 10/30/2006 8:55:49 AM | A | FAIL |
|
|
dave; Phone #: ###-#### Internet Inspection Request from: Marsha water heater pan is too small to allow combustion air or to clean filter, pipe pan drain to garage floor.
|