Inspections for the day of: Monday, October 30, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00007 FIR-Aging Inspection10/30/200610/30/200610/31/2006 12:05:57 PM DEFR
FIR06-00006 FIR-Aging Inspection10/30/200610/30/200610/31/2006 12:05:42 PM DEFR
FIR06-00677 INSP-Sprinkler Rough-in10/27/200610/30/200610/31/2006 9:17:08 AMPPART
OH rough-in for cover is okay except as noted on approved plans, one ssu is missing abve the restroom, one head at a new entryway is not yet installed, annular space between the new wall and existing freezer wall may not be properly covered.
FIR06-00797 INSP-Final Inspection10/30/200610/30/200610/31/2006 9:14:28 AMPPART
Fire alarm tested satisfactory, need to replace the damaged riser mounted flow switch as the housing base is cracked and the flex conduit and switch cover cannot be secured.
BLD06-02060 FIRE-Final Inspection10/30/200610/30/200610/30/2006 3:20:11 PMPNR
Pending alarm and sprinkler permit finals prior to life safety final, confrence room 705 is not yet complete, need to mount fire extinguishers as discussed.
FIR06-00679 INSP-Final Inspection10/30/200610/30/200610/30/2006 3:18:46 PMPPART
Need to relocate one head in the break room as discussed.
FIR06-00666 INSP-Final Inspection10/30/200610/30/200610/30/2006 3:18:01 PMPPART
Fire alarm work is acceptable pending completion of confrence room 705 and the associated notification device which is not installed at this time.
FIR06-00788 INSP-Final Inspection10/26/200610/30/200610/30/2006 1:46:15 PMAPASS
Required corrections have been verified for completion. The hood suppression system functioned properly under test conditions, inspection passed.
FIR06-00540 INSP-Sprinkler Rough-in/Hydro10/27/200610/30/200610/30/2006 12:57:27 PMAPART
Second floor NW quad OH hydrostatic test passed. Rough-in is good for cover at the drop ceiling areas, noted one ssu in the electrical room which needs to be relocated as discussed.
FIR06-00639 INSP-Sprinkler Rough-in/Hydro10/27/200610/30/200610/30/2006 11:54:24 AMAPART
OH hydrostatic test for the 4th floor passed, items noted on previous c/n for the 4th floor have been completed.