Inspections for the day of: Tuesday, October 30, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-04432 ELE-Aging Inspection10/30/200710/30/200711/2/2007 3:47:29 PM PASS
ELE07-03665 Conference10/30/200710/30/200710/30/2007 4:13:17 PMPPART
Phone #: ###-#### Internet Inspection Request from: Bob Glenn
talked about 50% rule and location of disconnect
ELE07-01609 Electrical Rough-In10/30/200710/30/200710/30/2007 3:26:19 PMPPART
rocky - ok to cover on 3 units on right side - please call 15 mintes prior to inspection Phone #: ###-####
3 units on the south side
ELE07-03655 Permanent Service10/30/200710/30/200710/30/2007 2:59:35 PMPFAIL
robert Phone #: ###-####
358.30 Securing and Supporting.
EMT shall be installed as a complete system as provided in Article 300 and shall be securely fastened in place and supported
250.52 Grounding Electrodes.
(A) Electrodes Permitted for Grounding.
(1) Metal Underground Water Pipe. Interior metal water piping located more than 1.52 m (5 ft) from the point of entrance to the building shall not be used as a part of the grounding electrode system or as a conductor to interconnect electrodes that are part of the grounding electrode system.

110.26 Spaces About Electrical Equipment.
(D) Illumination. Illumination shall be provided for all working spaces about service equipment, switchboards, panelboards, or motor control centers installed indoors. Additional lighting outlets shall not be required where the work space is illuminated by an adjacent light source or as permitted by 210.70(A)(1), Exception No. 1, for switched receptacles. In electrical equipment rooms, the illumination shall not be controlled by automatic means only.
ELE07-03667 Conference10/30/200710/30/200710/30/2007 2:08:04 PMPPART
roger Phone #: ###-####
talked about location of disconnect and grounding
ELE07-02062 Final10/30/200710/30/200710/30/2007 1:41:02 PMPPART
Scheduled by a contractor via Hello! on 10/30/2007 at 6:53:58 AM. Contact: ###-####.
kitchen bathrooms janitor closet and assembly room ok anop
ELE07-03669 Final10/30/200710/30/200710/30/2007 1:01:03 PMPPART
lloyd Phone #: ###-####
I marked the exit lights that I haven't seen because of tiles or were not secured within 12 in of boxes. The rest are ok.
ELE07-03658 Final10/29/200710/30/200710/30/2007 10:14:29 AMANR
renea Phone #: ###-####
I checked all receps some did not protrude from the metal covers .015 in.
No record of R/I inspection scott said that mike had seen it under another permit so I recommended that he have mike come out to see if he could remember the R/I inspection
ELE07-03478 Electrical Rough-In10/29/200710/30/200710/30/2007 9:56:37 AMAPART
Randy is the contact electrician, his number is ###-####. Phone #: ###-#### Internet Inspection Request from: Heather Packer
west wall ok
ELE07-02593 Electrical Rough-In10/26/200710/30/200710/30/2007 9:29:25 AMAPASS
Call 10 minutes early and meet in hospital lobby. Phone #: ###-#### Internet Inspection Request from: mark morris
ELE07-03637 Electrical Rough-In10/26/200710/30/200710/29/2007 12:03:36 PMACANC
zane Phone #: ###-#### Inspection cancelled from web by: Patricia Smith