ELE06-04432
| ELE-Aging Inspection | 10/30/2007 | 10/30/2007 | 11/2/2007 3:47:29 PM | | PASS |
|
|
|
ELE07-03665
| Conference | 10/30/2007 | 10/30/2007 | 10/30/2007 4:13:17 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Bob Glenn talked about 50% rule and location of disconnect
|
ELE07-01609
| Electrical Rough-In | 10/30/2007 | 10/30/2007 | 10/30/2007 3:26:19 PM | P | PART |
|
|
rocky - ok to cover on 3 units on right side - please call 15 mintes prior to inspection Phone #: ###-#### 3 units on the south side
|
ELE07-03655
| Permanent Service | 10/30/2007 | 10/30/2007 | 10/30/2007 2:59:35 PM | P | FAIL |
|
|
robert Phone #: ###-#### 358.30 Securing and Supporting. EMT shall be installed as a complete system as provided in Article 300 and shall be securely fastened in place and supported 250.52 Grounding Electrodes. (A) Electrodes Permitted for Grounding. (1) Metal Underground Water Pipe. Interior metal water piping located more than 1.52 m (5 ft) from the point of entrance to the building shall not be used as a part of the grounding electrode system or as a conductor to interconnect electrodes that are part of the grounding electrode system.
110.26 Spaces About Electrical Equipment. (D) Illumination. Illumination shall be provided for all working spaces about service equipment, switchboards, panelboards, or motor control centers installed indoors. Additional lighting outlets shall not be required where the work space is illuminated by an adjacent light source or as permitted by 210.70(A)(1), Exception No. 1, for switched receptacles. In electrical equipment rooms, the illumination shall not be controlled by automatic means only.
|
ELE07-03667
| Conference | 10/30/2007 | 10/30/2007 | 10/30/2007 2:08:04 PM | P | PART |
|
|
roger Phone #: ###-#### talked about location of disconnect and grounding
|
ELE07-02062
| Final | 10/30/2007 | 10/30/2007 | 10/30/2007 1:41:02 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 10/30/2007 at 6:53:58 AM. Contact: ###-####. kitchen bathrooms janitor closet and assembly room ok anop
|
ELE07-03669
| Final | 10/30/2007 | 10/30/2007 | 10/30/2007 1:01:03 PM | P | PART |
|
|
lloyd Phone #: ###-#### I marked the exit lights that I haven't seen because of tiles or were not secured within 12 in of boxes. The rest are ok.
|
ELE07-03658
| Final | 10/29/2007 | 10/30/2007 | 10/30/2007 10:14:29 AM | A | NR |
|
|
renea Phone #: ###-#### I checked all receps some did not protrude from the metal covers .015 in. No record of R/I inspection scott said that mike had seen it under another permit so I recommended that he have mike come out to see if he could remember the R/I inspection
|
ELE07-03478
| Electrical Rough-In | 10/29/2007 | 10/30/2007 | 10/30/2007 9:56:37 AM | A | PART |
|
|
Randy is the contact electrician, his number is ###-####. Phone #: ###-#### Internet Inspection Request from: Heather Packer west wall ok
|
ELE07-02593
| Electrical Rough-In | 10/26/2007 | 10/30/2007 | 10/30/2007 9:29:25 AM | A | PASS |
|
|
Call 10 minutes early and meet in hospital lobby. Phone #: ###-#### Internet Inspection Request from: mark morris
|
ELE07-03637
| Electrical Rough-In | 10/26/2007 | 10/30/2007 | 10/29/2007 12:03:36 PM | A | CANC |
|
|
zane Phone #: ###-#### Inspection cancelled from web by: Patricia Smith
|