Inspections for the day of: Tuesday, October 30, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00403 FIR-Aging Inspection10/30/200710/30/200711/2/2007 4:09:38 PM DEFR
Under construction.
FIR07-00146 INSP-Sprinkler Rough-in10/29/200710/30/200710/31/2007 9:02:05 AMPDEFR
See inspection notes under the shell permit.
FIR07-00150 INSP-Sprinkler Rough-in10/29/200710/30/200710/31/2007 9:01:30 AMPDEFR
See inspection notes under the shell permit.
FIR07-00031 INSP-Sprinkler Rough-in10/29/200710/30/200710/31/2007 9:00:53 AMPDEFR
See inspection notes under the shell permit.
FIR07-00022 INSP-Sprinkler Rough-in10/29/200710/30/200710/31/2007 9:00:18 AMPDEFR
See inspection notes under the shell permit.
FIR06-00504 INSP-Sprinkler Rough-in10/29/200710/30/200710/31/2007 8:59:02 AMPPART
Conclusion of the 24 hr air test for the dry system passed within allowable pressure loss, corrections completed as noted for the common corridors on the 3rd-6th floors.
FIR07-00575 INSP-Sprinkler Rough-in/Hydro10/29/200710/30/200710/31/2007 8:55:34 AMPPART
OH hydrostatic test completed for both the wet and preaction systems.
FIR07-00711 INSP-Final Inspection10/26/200710/30/200710/30/2007 3:42:48 PMPFAIL
Inspection failed per K. Roule due to notification appliance synchronization issues.
FIR07-00857 INSP-Sprinkler Rough-in10/30/200710/30/200710/30/2007 3:34:11 PMPPART
Required corrections have been made, overhead install is approved for cover at the drop ceilings.
BLD07-02051 FIRE-Final Inspection10/30/200710/30/200710/30/2007 12:28:09 PMPPASS
Fire life safety final passed per site inspection completed by K. Roule, corrections are complete.
BLD07-02051 FIRE-Supply Line Hydro10/29/200710/30/200710/30/2007 12:27:03 PMADEFR
Inspection intended for a life safety final.
FIR07-00803 INSP-Sprinkler Rough-in10/29/200710/30/200710/30/2007 12:26:01 PMAPART
Okay for sheetrock install at the basement level and the first floor restrooms, contractor to comply with listed min. spacing requirements of the residential heads installed, noted possible light fixture obstructions due to close proximity of heads and electrical junction boxes at some locations, will need resubmitted plans at next inspection for verification of field mods.
FIR07-00304 INSP-Final Inspection10/26/200710/30/200710/30/2007 12:17:42 PMAFAIL
Pendent heads adjacent to the east roll up door exceed noted system design spacing of 100ft2 max.
BLD07-00798 FIRE-Final Inspection10/26/200710/30/200710/30/2007 12:14:52 PMAPART
Fire life safety final pending project related fire sprinkler permit final.
FIR07-00277 INSP-Final Inspection10/26/200710/30/200710/30/2007 12:13:05 PMAPASS
Fire alarm work passed final inspection, permit finaled.
BLD07-02058 BLD-Final10/30/200710/30/200710/30/2007 10:03:30 AMAPASS
Racks are complete, inspection passed.
FIR07-00774 INSP-Final Inspection10/30/200710/30/200710/30/2007 9:32:03 AMAPASS
Fire alarm work passed inspection, permit finaled.
FIR07-00344 INSP-Final Inspection10/30/200710/30/200710/30/2007 9:31:21 AMAPASS
Return trip for re-inspection of the two new dry systems. Corrections completed, acceptance and trip testing passed per site visit by K. Roule.
BLD07-01859 FIRE-Final Inspection10/26/200710/30/200710/29/2007 3:22:16 PMACANC
mark Phone #: ###-#### Inspection cancelled from web by: Cathy Chiles