FIR07-00403
| FIR-Aging Inspection | 10/30/2007 | 10/30/2007 | 11/2/2007 4:09:38 PM | | DEFR |
|
|
Under construction.
|
FIR07-00146
| INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/31/2007 9:02:05 AM | P | DEFR |
|
|
See inspection notes under the shell permit.
|
FIR07-00150
| INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/31/2007 9:01:30 AM | P | DEFR |
|
|
See inspection notes under the shell permit.
|
FIR07-00031
| INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/31/2007 9:00:53 AM | P | DEFR |
|
|
See inspection notes under the shell permit.
|
FIR07-00022
| INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/31/2007 9:00:18 AM | P | DEFR |
|
|
See inspection notes under the shell permit.
|
FIR06-00504
| INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/31/2007 8:59:02 AM | P | PART |
|
|
Conclusion of the 24 hr air test for the dry system passed within allowable pressure loss, corrections completed as noted for the common corridors on the 3rd-6th floors.
|
FIR07-00575
| INSP-Sprinkler Rough-in/Hydro | 10/29/2007 | 10/30/2007 | 10/31/2007 8:55:34 AM | P | PART |
|
|
OH hydrostatic test completed for both the wet and preaction systems.
|
FIR07-00711
| INSP-Final Inspection | 10/26/2007 | 10/30/2007 | 10/30/2007 3:42:48 PM | P | FAIL |
|
|
Inspection failed per K. Roule due to notification appliance synchronization issues.
|
FIR07-00857
| INSP-Sprinkler Rough-in | 10/30/2007 | 10/30/2007 | 10/30/2007 3:34:11 PM | P | PART |
|
|
Required corrections have been made, overhead install is approved for cover at the drop ceilings.
|
BLD07-02051
| FIRE-Final Inspection | 10/30/2007 | 10/30/2007 | 10/30/2007 12:28:09 PM | P | PASS |
|
|
Fire life safety final passed per site inspection completed by K. Roule, corrections are complete.
|
BLD07-02051
| FIRE-Supply Line Hydro | 10/29/2007 | 10/30/2007 | 10/30/2007 12:27:03 PM | A | DEFR |
|
|
Inspection intended for a life safety final.
|
FIR07-00803
| INSP-Sprinkler Rough-in | 10/29/2007 | 10/30/2007 | 10/30/2007 12:26:01 PM | A | PART |
|
|
Okay for sheetrock install at the basement level and the first floor restrooms, contractor to comply with listed min. spacing requirements of the residential heads installed, noted possible light fixture obstructions due to close proximity of heads and electrical junction boxes at some locations, will need resubmitted plans at next inspection for verification of field mods.
|
FIR07-00304
| INSP-Final Inspection | 10/26/2007 | 10/30/2007 | 10/30/2007 12:17:42 PM | A | FAIL |
|
|
Pendent heads adjacent to the east roll up door exceed noted system design spacing of 100ft2 max.
|
BLD07-00798
| FIRE-Final Inspection | 10/26/2007 | 10/30/2007 | 10/30/2007 12:14:52 PM | A | PART |
|
|
Fire life safety final pending project related fire sprinkler permit final.
|
FIR07-00277
| INSP-Final Inspection | 10/26/2007 | 10/30/2007 | 10/30/2007 12:13:05 PM | A | PASS |
|
|
Fire alarm work passed final inspection, permit finaled.
|
BLD07-02058
| BLD-Final | 10/30/2007 | 10/30/2007 | 10/30/2007 10:03:30 AM | A | PASS |
|
|
Racks are complete, inspection passed.
|
FIR07-00774
| INSP-Final Inspection | 10/30/2007 | 10/30/2007 | 10/30/2007 9:32:03 AM | A | PASS |
|
|
Fire alarm work passed inspection, permit finaled.
|
FIR07-00344
| INSP-Final Inspection | 10/30/2007 | 10/30/2007 | 10/30/2007 9:31:21 AM | A | PASS |
|
|
Return trip for re-inspection of the two new dry systems. Corrections completed, acceptance and trip testing passed per site visit by K. Roule.
|
BLD07-01859
| FIRE-Final Inspection | 10/26/2007 | 10/30/2007 | 10/29/2007 3:22:16 PM | A | CANC |
|
|
mark Phone #: ###-#### Inspection cancelled from web by: Cathy Chiles
|