Inspections for the day of: Thursday, October 30, 2008.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00618 INSP-Final Inspection10/30/200810/30/200810/30/2008 4:42:58 PMPNR
Noted trouble at the panel due to nac fault, three sprinkler tampers closed due to work in progress,system is not ready for final inspection at this time.
FIR08-00596 INSP-Sprinkler Rough-in/Hydro10/30/200810/30/200810/30/2008 4:40:09 PMPPART
Sprinkler installation at the 2nd floor hard lid ceiling above the stairway is approved for cover, minor adjustments made while on site, see plans for locations okayed wtih todays date.
FIR08-00595 INSP-Sprinkler Rough-in10/29/200810/30/200810/30/2008 4:36:45 PMPNR
BLD07-03215 FIRE-Final Inspection10/30/200810/30/200810/30/2008 3:10:10 PMPPASS
C/N finished, final fire life safety inspection passed.
FIR06-00621 INSP-Alarm Testing10/27/200810/30/200810/30/2008 2:39:37 PMAPART
Fire alarm notification devices tested okay at the 2nd floor mechanical room areas, common corridor, restrooms, locker room and mech. penthouse, EOL voltage is satisfactory,
BLD08-02224 FIRE-Final Inspection10/29/200810/30/200810/30/2008 1:47:43 PMPFAIL
Some items on the previous correction notice are not yet finished including exit signs and EM lights still in need of repair at various locations, also missing panic hardware at the northeast pair of exit doors to the pool enclosure, noted three fire extinguishers not yet installed. Inspection to be rescheduled as discussed when work is completed.
BLD08-00985 FIRE-Final Inspection10/30/200810/30/200810/30/2008 12:58:04 PMPFAIL
Need to provide verification the two access control egress doors are interconnected to the fire alarm control panel for power loss to the magnets upon alarm condition-see electrical sheet note 22 red lined annotation and fire code review notes for details. Also need to provide one missing exit sign at the east side per approved drawings.
FIR08-00521 FIR-Aging Inspection10/30/200810/30/200810/30/2008 12:53:29 PM DONE
Site visit confirmed building construction underway, work in progress.
FIR08-00514 INSP-Supply line flush10/29/200810/30/200810/30/2008 10:56:33 AMAPART
UG fire supply line flush completed satisfactory.
FIR08-00727 INSP-Final Inspection10/29/200810/30/200810/30/2008 10:03:10 AMAPASS
Fire sprinkler permit work passed final inspection.
FIR08-00239 INSP-Sprinkler Rough-in/Hydro10/29/200810/30/200810/30/2008 9:31:03 AMAFAIL
Insulation at the concealed non-sprinklered attic pockets is still missing, will need inspection prior to cover approval.
FIR08-00449 FIR-Aging Inspection10/30/200810/30/200810/30/2008 9:17:26 AM DONE
Work in progress, site construction underway.
BLD08-01853 FIRE-Final Inspection10/29/200810/30/200810/30/2008 9:16:41 AMAPASS
Corrections verified for completion, fire life safety final inspection passed.