ELE09-01040
| Electrical Rough-In | 10/30/2009 | 10/30/2009 | 10/30/2009 3:55:35 PM | P | PASS |
|
|
bill Phone #: ###-#### ric ok, no esc this project
|
ELE09-01670
| Final | 10/30/2009 | 10/30/2009 | 10/30/2009 3:43:32 PM | P | PASS |
|
|
chad Phone #: ###-#### ok to final
|
ELE09-02054
| Final | 10/30/2009 | 10/30/2009 | 10/30/2009 3:28:52 PM | P | PASS |
|
|
Mike Phone #: ###-#### ok to final, no esc this project
|
ESC09-00456
| General Inspection | 10/30/2009 | 10/30/2009 | 10/30/2009 3:16:04 PM | P | PASS |
|
|
looked ok
|
ESC09-00232
| General Inspection | 10/30/2009 | 10/30/2009 | 10/30/2009 3:15:15 PM | P | PASS |
|
|
looked ok, landscapers on site
|
ESC09-00463
| General Inspection | 10/30/2009 | 10/30/2009 | 10/30/2009 3:14:21 PM | P | PASS |
|
|
looked ok
|
ESC09-00599
| General Inspection | 10/30/2009 | 10/30/2009 | 10/30/2009 3:13:44 PM | P | PASS |
|
|
looked ok
|
ESC08-00761
| General Inspection | 10/30/2009 | 10/30/2009 | 10/30/2009 3:13:00 PM | P | PASS |
|
|
looked ok
|
ESC09-00181
| General Inspection | 10/30/2009 | 10/30/2009 | 10/30/2009 3:12:20 PM | P | PASS |
|
|
looked ok, muddy, utility road crossing underway
|
ELE09-01826
| Electrical Rough-In | 10/29/2009 | 10/30/2009 | 10/30/2009 3:06:03 PM | P | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Randy Vail ok to cover u/g anop
|
ELE09-02104
| Electrical Rough-In | 10/29/2009 | 10/30/2009 | 10/30/2009 2:05:23 PM | A | PART |
|
|
Gary Phone #: ###-#### u/g house to shed only ok to cover, called, needs to provide concrete encased electrode, no esc this project
|
ELE09-01845
| Electrical Rough-In | 10/29/2009 | 10/30/2009 | 10/30/2009 1:36:00 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: JENNY EMEL walls and hard lids ok to cover
|
ELE09-02124
| Temporary Service | 10/30/2009 | 10/30/2009 | 10/30/2009 12:29:57 PM | P | PASS |
|
|
justin Phone #: ###-#### - please call 1/2 hr prior t/s u/g n ok
|
ELE09-02112
| Permanent Service | 10/29/2009 | 10/30/2009 | 10/30/2009 11:50:02 AM | P | PASS |
|
|
Shane Phone #: ###-#### p/s o/h rec ok, no esc this project
|
ELE09-02115
| Temporary Service | 10/29/2009 | 10/30/2009 | 10/30/2009 11:10:05 AM | A | FAIL |
|
|
Bret ###-#### called, left correction notice, NEC 312.5 shall provide abrasion protection for all conductors entering enclosure, 250.28 shall provide main bonding jumper, 250.92 shall provide raceway bonding at service, 406.8(B) 120v receptacles shall be listed weather resistant type, 408.4 shall provide clear and correct and concise circuit directory, 334.12 shall not use nm cable in wet or damp locations, 230.41 service conductors shall be insulated
|
ELE09-01467
| Final | 10/29/2009 | 10/30/2009 | 10/30/2009 10:51:18 AM | A | PASS |
|
|
final on new house, any questions call Rob @ ###-#### Phone #: ###-#### Internet Inspection Request from: Andy Rose ok to final
|
ELE09-02113
| Final | 10/29/2009 | 10/30/2009 | 10/30/2009 10:06:52 AM | A | PASS |
|
|
rob Phone #: ###-#### ok to final, no esc this project
|
ELE09-01931
| Final | 10/30/2009 | 10/30/2009 | 10/30/2009 9:43:45 AM | A | PASS |
|
|
ok to final, no esc this project
|
ELE09-01931
| Electrical Rough-In | 10/29/2009 | 10/30/2009 | 10/30/2009 9:42:30 AM | A | PASS |
|
|
electrical work is complete - please also do a final Phone #: ###-#### Internet Inspection Request from: Celinda Winters met contractor,ric ok, no esc this project
|
ELE09-02099
| Electrical Rough-In | 10/28/2009 | 10/30/2009 | 10/30/2009 9:41:20 AM | A | PASS |
|
|
underground uffer and pvc to pump concrete schudule to pour Monday Phone #: ###-#### Internet Inspection Request from: Scott Abbott called contractor, ok to pour, u/g at pad ok to pour, no esc this project
|
ELE09-01997
| Electrical Rough-In | 10/29/2009 | 10/30/2009 | 10/30/2009 9:02:37 AM | P | CANC |
|
|
Underground inspection only. Request inspection between 11:30-12:00, if possible. If not, as early in the afternoon as possible. Thank you. Phone #: ###-#### Internet Inspection Request from: Tracy Robertson Inspection cancelled from web by: Tracy Robertson
|
ELE09-01066
| Electrical Rough-In | 10/29/2009 | 10/30/2009 | 10/30/2009 8:48:16 AM | A | CANC |
|
|
RI inspection for the East wing Phone #: ###-#### Internet Inspection Request from: Spencer Mclean wrong permit called in, told contractor to recall with right permit
|
ELE09-01670
| Final | 10/29/2009 | 10/30/2009 | 10/30/2009 8:31:42 AM | A | NH |
|
|
Chad Phone #: ###-#### called contractor to tell to call when somebody can meet inspector on site,
|
ELE09-00528
| Final | 10/29/2009 | 10/30/2009 | 10/30/2009 8:22:28 AM | A | PASS |
|
|
Access code 02430. Front door should also be unlocked Phone #: ###-#### Internet Inspection Request from: Joe Thomas corrections made, ok to final
|
ELE09-00589
| Final | 10/29/2009 | 10/30/2009 | 10/30/2009 8:21:07 AM | A | PASS |
|
|
Access code 02430. Front door should also be unlocked Phone #: ###-#### Internet Inspection Request from: Joe Thomas ok to final
|