Inspections for the day of: Tuesday, October 30, 2012.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR12-00318 INSP-Sprinkler Rough-in10/29/201210/30/201210/31/2012 4:55:28 PMPPART
Overhead rough-in at the upper warehouse passed- see plans for dated annotations.
BLD10-02844 FIRE-Final Inspection10/25/201210/30/201210/31/2012 4:44:27 PMAPASS
Fire life safety finaled.
BLD12-00427 FIRE-Final Inspection10/25/201210/30/201210/31/2012 4:43:34 PMAPASS
Fire life safety passed.
BLD12-02352 FIRE-Final Inspection10/30/201210/30/201210/30/2012 4:45:52 PMPPASS
Life safety inspection passed.
BLD12-02114 FIRE-Final Inspection10/30/201210/30/201210/30/2012 4:45:03 PMPPASS
Life safety passed.
FIR12-00528 INSP-Sprinkler Rough-in/Hydro10/29/201210/30/201210/30/2012 4:40:59 PMPPART
OH hydrostatic test completed.
FIR12-00527 INSP-Sprinkler Rough-in/Hydro10/29/201210/30/201210/30/2012 4:40:13 PMPPART
OH hydrostatic test passed.
FIR12-00483 INSP-Sprinkler Rough-in10/30/201210/30/201210/30/2012 4:02:09 PMPCANC
Overbooked
BLD12-02115 FIRE-Final Inspection10/30/201210/30/201210/30/2012 4:00:34 PMPPASS
Inspection passed. Fire life safety finaled.
BLD12-02349 FIRE-Final Inspection10/30/201210/30/201210/30/2012 3:59:37 PMPPASS
Scope of work completed. Fire life safety passed.
FIR12-00287 INSP-Sprinkler Rough-in10/29/201210/30/201210/30/2012 3:31:38 PMAFAIL
Extended coverage SW head at the stairway landing is blocked by a beam, need access to view new main piping and tie-ins above the existing ceiling 1st floor, installation must match plan or provide new calcs per review notes- noted additional 90's at every drop and one extra 2 1/2" 90 2nd floor.
FIR12-00426 INSP-Final Inspection10/29/201210/30/201210/30/2012 1:40:50 PMAPASS
Inspection passed. Fire sprinkler permit finaled.
FIR12-00571 INSP-Final Inspection10/29/201210/30/201210/30/2012 1:19:04 PMAFAIL
Activation of the 3 gallon ansul hood system failed to shut down gas supply at the appliances. Hood suppression system at the back kitchen cook line operated correctly under test conditions.
FIR12-00447 INSP-Final Inspection10/30/201210/30/201210/30/2012 1:12:48 PMAFAIL
New pendent head to be added per the approved plans at the kitchen area is not yet installed. Remainder of permit work is finished.
BLD11-00939 FIRE-Final Inspection10/29/201210/30/201210/30/2012 9:15:34 AMACANC
Meet in B25 at Paul''s office Phone #: ###-#### >> Inspection requested via web by Greg Kirkes Inspection cancelled from web by: Greg Kirkes
FIR12-00489 INSP-Final Inspection10/29/201210/30/201210/30/2012 12:00:00 AMADONE
Access control doors functioned properly. I told Art to provide as-built drawings showing the actual locations of the push buttons. The pull station in the riser room did not function properly. I let Art know that I would contact Code Enforcement regarding the pull station, and it would not affect his permit.