FIR12-00318
| INSP-Sprinkler Rough-in | 10/29/2012 | 10/30/2012 | 10/31/2012 4:55:28 PM | P | PART |
|
|
Overhead rough-in at the upper warehouse passed- see plans for dated annotations.
|
BLD10-02844
| FIRE-Final Inspection | 10/25/2012 | 10/30/2012 | 10/31/2012 4:44:27 PM | A | PASS |
|
|
Fire life safety finaled.
|
BLD12-00427
| FIRE-Final Inspection | 10/25/2012 | 10/30/2012 | 10/31/2012 4:43:34 PM | A | PASS |
|
|
Fire life safety passed.
|
BLD12-02352
| FIRE-Final Inspection | 10/30/2012 | 10/30/2012 | 10/30/2012 4:45:52 PM | P | PASS |
|
|
Life safety inspection passed.
|
BLD12-02114
| FIRE-Final Inspection | 10/30/2012 | 10/30/2012 | 10/30/2012 4:45:03 PM | P | PASS |
|
|
Life safety passed.
|
FIR12-00528
| INSP-Sprinkler Rough-in/Hydro | 10/29/2012 | 10/30/2012 | 10/30/2012 4:40:59 PM | P | PART |
|
|
OH hydrostatic test completed.
|
FIR12-00527
| INSP-Sprinkler Rough-in/Hydro | 10/29/2012 | 10/30/2012 | 10/30/2012 4:40:13 PM | P | PART |
|
|
OH hydrostatic test passed.
|
FIR12-00483
| INSP-Sprinkler Rough-in | 10/30/2012 | 10/30/2012 | 10/30/2012 4:02:09 PM | P | CANC |
|
|
Overbooked
|
BLD12-02115
| FIRE-Final Inspection | 10/30/2012 | 10/30/2012 | 10/30/2012 4:00:34 PM | P | PASS |
|
|
Inspection passed. Fire life safety finaled.
|
BLD12-02349
| FIRE-Final Inspection | 10/30/2012 | 10/30/2012 | 10/30/2012 3:59:37 PM | P | PASS |
|
|
Scope of work completed. Fire life safety passed.
|
FIR12-00287
| INSP-Sprinkler Rough-in | 10/29/2012 | 10/30/2012 | 10/30/2012 3:31:38 PM | A | FAIL |
|
|
Extended coverage SW head at the stairway landing is blocked by a beam, need access to view new main piping and tie-ins above the existing ceiling 1st floor, installation must match plan or provide new calcs per review notes- noted additional 90's at every drop and one extra 2 1/2" 90 2nd floor.
|
FIR12-00426
| INSP-Final Inspection | 10/29/2012 | 10/30/2012 | 10/30/2012 1:40:50 PM | A | PASS |
|
|
Inspection passed. Fire sprinkler permit finaled.
|
FIR12-00571
| INSP-Final Inspection | 10/29/2012 | 10/30/2012 | 10/30/2012 1:19:04 PM | A | FAIL |
|
|
Activation of the 3 gallon ansul hood system failed to shut down gas supply at the appliances. Hood suppression system at the back kitchen cook line operated correctly under test conditions.
|
FIR12-00447
| INSP-Final Inspection | 10/30/2012 | 10/30/2012 | 10/30/2012 1:12:48 PM | A | FAIL |
|
|
New pendent head to be added per the approved plans at the kitchen area is not yet installed. Remainder of permit work is finished.
|
BLD11-00939
| FIRE-Final Inspection | 10/29/2012 | 10/30/2012 | 10/30/2012 9:15:34 AM | A | CANC |
|
|
Meet in B25 at Paul''s office Phone #: ###-#### >> Inspection requested via web by Greg Kirkes Inspection cancelled from web by: Greg Kirkes
|
FIR12-00489
| INSP-Final Inspection | 10/29/2012 | 10/30/2012 | 10/30/2012 12:00:00 AM | A | DONE |
|
|
Access control doors functioned properly. I told Art to provide as-built drawings showing the actual locations of the push buttons. The pull station in the riser room did not function properly. I let Art know that I would contact Code Enforcement regarding the pull station, and it would not affect his permit.
|