Inspections for the day of: Thursday, October 30, 2014.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR14-00449 INSP-Final Inspection10/30/201410/30/201410/30/2014 5:27:07 PMPNR
Items noted include; duct detectors and door holds throughout are not yet ready for testing or inspection, SD's for door holds at two locations second floor need relocated, post signage at the door to the FACP room, zones per plan do not match field install, HD at zone 17 has been deleted- however plans item #6 show to remain, need to provide as-builts reflecting changes prior to final, two knox boxes are posted, MP station is located at the main entry not at the fire riser room. Items tested today include; sprinkler riser supervision, SD at the panel, batteries, Netcon rating, offsite monitoring. Discussed remote indicators for duct detectors.
BLD14-01440 FIRE-Final Inspection10/30/201410/30/201410/30/2014 5:11:06 PMPPART
Final pending project related fire alarm permit work. Need to add two exit discharge lights second floor exterior stair landings south side. Okayed for TCO per S. Arellano.
FIR14-00783 INSP-Sprinkler Rough-in10/30/201410/30/201410/30/2014 5:08:04 PMPPART
Ref. to stamped plans for portions okayed for bury.
FIR14-00783 INSP-Sprinkler Rough-in10/29/201410/30/201410/30/2014 12:26:56 PMAPART
UG fire supply line ductile risers and stubs to a point approx. 15' beyond the stem wall as marked/dated on approved plans okayed for bury.
FIR14-00222 INSP-Final Inspection10/30/201410/30/201410/30/2014 11:25:50 AMPCANC
Please call when you are on your way Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello