Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-03420 Electrical Rough-In10/30/201910/30/201910/30/2019 4:53:23 PMPPASS
Jose Phone #: ###-####
Phase 2 grid rough in ok cover
ELE19-03645 Final10/30/201910/30/201910/30/2019 1:28:50 PMPPASS
Phone #: ###-#### Inspection requested via web by Andrea Creek Final ok
ELE19-03829 Electrical Rough-In10/30/201910/30/201910/30/2019 11:55:25 AMAPASS
Rough-in inspection for lightning ground loop along north side of building. Phone #: ###-#### Inspection requested via web by Cathy Duchek
Temp power supply to 50 amp twist locks shall have GFCI protection as per 590.6(B).
Lightning loop complete. Rough in ok cover.
ELE19-00601 Electrical Rough-In10/29/201910/30/201910/30/2019 11:20:27 AMANR
2nd floor wall cover. Danny is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen
Prewalk south and west room. Nail plate all holes used to run MC cable that do not maintain 1 1/4" from framing surfaces. Secure MC above areas that will be sheet rocked, corners and some hanging below ceilings. ENT runs shall not have more than 360 degrees of bends. Will recall when ready.
ELE19-04174 Temporary Service10/29/201910/30/201910/30/2019 10:37:33 AMAPASS
Phone #: ###-#### Inspection requested via web by Hidajet Zahic t/s u/g n ok
ELE19-03212 Final10/29/201910/30/201910/30/2019 10:05:57 AMAPASS
garage code 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE19-01482 Final10/29/201910/30/201910/30/2019 9:46:25 AMAFAIL
Electrical final inspection needed for "left stairwell units" #301, #302, #201,#202, #101 and #102 Thank you Phone #: ###-#### Inspection requested via web by Angela Stears
110.3- Panel cover door shall be complete as per listing. 101.
210.52(C)- Receptacle outlets installed to serve kitchen counter top space at end of peninsula shall not be locatedmre than 6" back under overhang. All units.
408.4- Circuit directory shall be complete. 101.