Inspections for the day of: Wednesday, October 30, 2019.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBrian Scoles
TitleMEC INSPECTOR
Phone #914-4915
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00220 Final10/29/201910/30/201910/30/2019 3:45:12 PMPPASS
Phone #: ###-#### Inspection requested via web by Jared Wilson- furnace a/c coil co locking caps gas piping ok
MEC19-03375 Final10/29/201910/30/201910/30/2019 3:23:07 PMPPASS
Mechanical Gas Fireplace Final Inspection. Manual is in kitchen drawer right of stove. Please call Kelly @ ###-#### when heading there. Phone #: ###-#### Inspection requested via web by Dan Otero- fireplace final ok
MEC19-01441 Final10/30/201910/30/201910/30/2019 2:49:06 PMPPART
Phone #: ###-#### Inspection requested via web by Kelton Tackett- need electrical permit issued for electrical work on boiler- mec permit is attached to building permit from 2012- need to verify bld is right or did it need one- Talked with Kelton onsite he will check into this and let me know- Boiler and gas piping ok- will final out once issues have been resolved
MEC19-03852 Final10/30/201910/30/201910/30/2019 2:19:21 PMPFAIL
Jake is the contact Phone #: ###-#### Inspection requested via web by stan lillquist-
1- need roof access fire riser room locked up
2- need to remove all ceiling tiles around register to finish R/I inspection on insulation duct and registers and have ladder onsite for inspection
MEC19-04801 Rough-in10/29/201910/30/201910/30/2019 1:58:42 PMPFAIL
Phone #: ###-#### Inspection requested via web by Oleg Chervak- need to seal all R/A boots- need to seal dryer duct to termination box
MEC19-04801 Pressure Test10/29/201910/30/201910/30/2019 1:57:17 PMPPASS
Phone #: ###-#### Inspection requested via web by Oleg Chervak- 20lb gas pass tagged meter location
MEC19-02591 Rough-in10/30/201910/30/201910/30/2019 1:30:19 PMPFAIL
Ceiling cover for grid ceiling installation Phone #: ###-#### Inspection requested via web by Robin Cox- rm 142 needs supply duct hooked up to register- rm 109 needs flex ducting supported off grid- rm116 need supply duct supported off grid- rm 130a need to verify that electrical closet is not getting an ceiling in it for transfer ducting wasnt shown on print to get enclosed around panel- Rest is good- still need to look at unit heaters and roof penetrations
MEC19-04817 Final10/24/201910/30/201910/30/2019 12:47:24 PMPNR
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- still installing- recall in when ready- went over onsite with Travis
MEC19-04817 Pressure Test10/24/201910/30/201910/30/2019 12:46:01 PMPPASS
INSTALLER TRAVIS ###-#### Phone #: ###-#### Inspection requested via web by Aaron Alandt- 20lb gas pass
MEC19-04037 Rough-in10/29/201910/30/201910/30/2019 11:21:40 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- R/I ok- need to seal R/A can where outside air was removed and patched by final- could not see if sealed on inside since filter was installed in can
MEC19-04037 Pressure Test10/29/201910/30/201910/30/2019 11:20:03 AMAPASS
Phone #: ###-#### Inspection requested via web by Gary Reeves- 20lb gas pass- tagged meter location
MEC19-04546 Rough-in10/29/201910/30/201910/30/2019 10:52:38 AMAFAIL
GARI ###-####
MANUAL UNDER UNIT W/REMOTE Phone #: ###-#### Inspection requested via web by Mike Almanza- draft stop to flue does not have 1" clearance to combustible- offset inside chase doesnt have 1" clearance to vertical 2x4
MEC19-04137 Final10/29/201910/30/201910/30/2019 10:25:05 AMAPASS
Phone #: ###-#### Inspection requested via web by RaChelle Frisbee- final ok- card signed- engineer approved relocation of RTU via stamped document
MEC19-02931 Final10/29/201910/30/201910/30/2019 9:56:04 AMAFAIL
Back door is open Phone #: ###-#### Inspection requested via web by Konrad Swartz- need locking caps on a/c service ports- rest is good
MEC19-01310 Final10/28/201910/30/201910/30/2019 9:28:41 AMAPASS
our techs will be on site by 8:30 to do necessary repairs. Will take approx. 1 hour. thank you!! Phone #: ###-#### Inspection requested via web by Denise Colin- a/c coil co locking caps ok
MEC19-04688 Final10/23/201910/30/201910/30/2019 8:53:06 AMAPASS
Please call prior Ray or Viola Martin ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- furnace only co ok
MEC19-04492 Final10/30/201910/30/201910/30/2019 8:17:04 AMAFAIL
early as possible- ###-####- furnace a/c coil co ok- need locking caps on a/c service ports- send pic for reinspect
MEC18-05961 Mec-Aging Inspection10/30/201910/30/201910/30/2019 7:51:11 AM FAIL
contractor needs to schedule inspection- bld still open- permit will expire next aging
MEC18-04405 Mec-Aging Inspection10/30/201910/30/201910/30/2019 7:50:07 AM CANC
no calls- no activity- bld still open- contractor needs to schedule final
MEC18-05831 Mec-Aging Inspection10/30/201910/30/201910/30/2019 7:47:52 AM CANC
MEC18-05831 DOC - Permit Expired10/30/201910/30/201910/30/2019 7:47:45 AMAPASS
no calls- no activity
MEC19-03757 Final10/29/201910/30/201910/29/2019 2:02:48 PMACANC
ANY QUESTIONS YOU CAN CALL SAM THE PROJECT MANAGER
###-#### Phone #: ###-#### >> Inspection requested via web by Aaron Alandt Inspection cancelled from web by: Aaron Alandt