Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-00431 Conference10/30/201910/30/201910/30/2019 1:12:05 PMADONE
11:00 am - Had another inspector report that there could possibly be issues with the HVAC install on this project. I reopened the permit and went and met the mechanical contractor and the owner on site. They have turned the sunroom into a shower room. currently there is supply grills installed on the floor and a return grill in the room. I explained to them that we can't have the floor registers in the shower area, and we need to remove the return grill from the shower. they are looking at a couple diffrent options to try to seperate the shower area from the rest of the room. additionally they have a ducted return grill in the bedroom where they have built a bathroom without seprrating it from the bedroom so I explained to them that we can't pull ducted return air from the room because of the bathroom. They are looking at the redesign options available to them. I instructed them to have new drawings submitted to the city of Boise.
MEC19-03524 Pressure Test10/29/201910/30/201910/30/2019 9:44:39 AMAPASS
JOHN IS THE JOB CONTACT ###-#### Phone #: ###-#### Inspection requested via web by BECCA DUMMER - 60lb gas pass
MEC18-04660 Mec-Aging Inspection10/30/201910/30/201910/30/2019 8:47:11 AM DONE
expired
MEC18-04660 DOC - Permit Expired10/30/201910/30/201910/30/2019 8:46:52 AMAPASS