Inspections for the day of: Monday, October 31, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00531 INSP-Alarm Testing10/31/200510/31/200510/31/2005 4:12:19 PMPPART
Devices tested satisfactory, final pending resubmittals for relocated av and address changes on duct detectors.
FIR05-00372 INSP-Final Inspection10/31/200510/31/200510/31/2005 4:10:08 PMPFAIL
Approval pending items remaining on correction notice including forward flow test, roof standpipe flow test, heads under overhead door at riser, resubmittals for box office changes, tenant demising wall coverage obstructions, lacking coverage in clock tower for combustibles, escutcheons at locations in theatre spaces.
FIR05-00528 INSP-Final Inspection10/28/200510/31/200510/31/2005 4:05:31 PMAPART
Overhead hydrostatic test passed inspection.
FIR05-00519 INSP-Alarm Testing10/28/200510/31/200510/31/2005 4:04:33 PMAPASS
Fire alarm inspected by Mary Froemke passed inspection, permit finaled.
FIR05-00475 INSP-Sprinkler Rough-in10/28/200510/31/200510/31/2005 4:02:57 PMAFAIL
Canopies are missing at confrence room heads, remove ssu as discussed.
FIR05-00459 INSP-Alarm Testing10/30/200510/31/200510/31/2005 4:01:39 PMAFAIL
Remove NAC A1:3 and speaker circut A1:3, revise duct detectors, NAC B4 circut is less than 21.6 EOL, verify wall mounted AV's are not blocked by video games when installed, check battery backup quantity allowed at theatres, partial inspection only no theatres inspected at this time.
BLD05-00850 FIRE-Final Inspection10/28/200510/31/200510/31/2005 3:56:27 PMAFAIL
Provide knox box and key as required, final pending shell sprinkler and alarm approval.
MIS05-00150 FIR-Final10/27/200510/31/200510/31/2005 12:22:53 PMAFAIL
Post max occupant load sign at the main entrance, repair emergency light at the back exit from kitchen.
BLD05-01706 FIRE-Final Inspection10/28/200510/31/200510/31/2005 11:54:28 AMAFAIL
Repair non-functioning emergency lights and exit sign, install missing door hardware at several locations, install tactile exit sign as shown on approved plans.
FIR05-00576 INSP-Conference10/28/200510/31/200510/31/2005 11:13:37 AMADONE
On site discussion regarding duct smoke detector locations.
BLD05-00311 FIRE-Final Inspection10/28/200510/31/200510/31/2005 10:02:14 AMAFAIL
Install emergency lights in the tailoring area as shown on approved plans, provide permanent suite address numbers, final pending shell permit approvals.
FIR05-00623 INSP-Alarm Testing10/31/200510/31/200510/31/2005 9:59:47 AMPPART
Fire alarm permit work for this TI space passed inspection, final pending shell permit approvals.
MIS05-00173 FIR-Final10/27/200510/31/200510/28/2005 5:10:51 PMPCANC
No time for this inspection due to BODO project inspections.