FIR05-00531
| INSP-Alarm Testing | 10/31/2005 | 10/31/2005 | 10/31/2005 4:12:19 PM | P | PART |
|
|
Devices tested satisfactory, final pending resubmittals for relocated av and address changes on duct detectors.
|
FIR05-00372
| INSP-Final Inspection | 10/31/2005 | 10/31/2005 | 10/31/2005 4:10:08 PM | P | FAIL |
|
|
Approval pending items remaining on correction notice including forward flow test, roof standpipe flow test, heads under overhead door at riser, resubmittals for box office changes, tenant demising wall coverage obstructions, lacking coverage in clock tower for combustibles, escutcheons at locations in theatre spaces.
|
FIR05-00528
| INSP-Final Inspection | 10/28/2005 | 10/31/2005 | 10/31/2005 4:05:31 PM | A | PART |
|
|
Overhead hydrostatic test passed inspection.
|
FIR05-00519
| INSP-Alarm Testing | 10/28/2005 | 10/31/2005 | 10/31/2005 4:04:33 PM | A | PASS |
|
|
Fire alarm inspected by Mary Froemke passed inspection, permit finaled.
|
FIR05-00475
| INSP-Sprinkler Rough-in | 10/28/2005 | 10/31/2005 | 10/31/2005 4:02:57 PM | A | FAIL |
|
|
Canopies are missing at confrence room heads, remove ssu as discussed.
|
FIR05-00459
| INSP-Alarm Testing | 10/30/2005 | 10/31/2005 | 10/31/2005 4:01:39 PM | A | FAIL |
|
|
Remove NAC A1:3 and speaker circut A1:3, revise duct detectors, NAC B4 circut is less than 21.6 EOL, verify wall mounted AV's are not blocked by video games when installed, check battery backup quantity allowed at theatres, partial inspection only no theatres inspected at this time.
|
BLD05-00850
| FIRE-Final Inspection | 10/28/2005 | 10/31/2005 | 10/31/2005 3:56:27 PM | A | FAIL |
|
|
Provide knox box and key as required, final pending shell sprinkler and alarm approval.
|
MIS05-00150
| FIR-Final | 10/27/2005 | 10/31/2005 | 10/31/2005 12:22:53 PM | A | FAIL |
|
|
Post max occupant load sign at the main entrance, repair emergency light at the back exit from kitchen.
|
BLD05-01706
| FIRE-Final Inspection | 10/28/2005 | 10/31/2005 | 10/31/2005 11:54:28 AM | A | FAIL |
|
|
Repair non-functioning emergency lights and exit sign, install missing door hardware at several locations, install tactile exit sign as shown on approved plans.
|
FIR05-00576
| INSP-Conference | 10/28/2005 | 10/31/2005 | 10/31/2005 11:13:37 AM | A | DONE |
|
|
On site discussion regarding duct smoke detector locations.
|
BLD05-00311
| FIRE-Final Inspection | 10/28/2005 | 10/31/2005 | 10/31/2005 10:02:14 AM | A | FAIL |
|
|
Install emergency lights in the tailoring area as shown on approved plans, provide permanent suite address numbers, final pending shell permit approvals.
|
FIR05-00623
| INSP-Alarm Testing | 10/31/2005 | 10/31/2005 | 10/31/2005 9:59:47 AM | P | PART |
|
|
Fire alarm permit work for this TI space passed inspection, final pending shell permit approvals.
|
MIS05-00173
| FIR-Final | 10/27/2005 | 10/31/2005 | 10/28/2005 5:10:51 PM | P | CANC |
|
|
No time for this inspection due to BODO project inspections.
|