Inspections for the day of: Tuesday, October 31, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03961 Electrical Rough-In10/31/200610/31/200610/31/2006 4:18:33 PMPPASS
dave - note: please call after insp. is completed ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to backfill gec
ELE06-04033 Temporary Service10/31/200610/31/200610/31/2006 3:47:28 PMPFAIL
Temp pole; Phone #: ###-#### Internet Inspection Request from: Ryan Christensen called, left corr notice, nec 312.5 all conductors entering enclosures shall have abrasion protection, 110.12(C) there shall be no broken or cut parts- panel, recpt, 230.28 service mast shall be adequate strength to support conductors,230.26 point of attachment of service drop conductors shall be minimum 10' above grade, 110.12(A) unused openings shall be closed (bottom raceway), 110.3(B) only breakers shall be used per mfgrs listing and labelling, BCC job id sticker shall be posted
ELE06-03406 Final10/31/200610/31/200610/31/2006 3:02:23 PMPPASS
Glen called about loose outside recpts, ok to final
ELE06-03380 Final10/30/200610/31/200610/31/2006 2:47:04 PMPPASS
Glen; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt called contr about panel door, ok to final
ELE06-03336 Final10/30/200610/31/200610/31/2006 2:40:47 PMPPASS
Glen; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt ok to final
ELE06-04032 Rough-In Permanent Service10/31/200610/31/200610/31/2006 1:15:14 PMPPASS
ron; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok, p/s u/g n ok
ELE06-04027 Rough-In Permanent Service10/31/200610/31/200610/31/2006 1:08:52 PMPPASS
jack; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ric ok, p/s u/g n ok
ELE06-04035 Rough-In Permanent Service10/31/200610/31/200610/31/2006 1:07:55 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called contr, he says flourescent lights in closet, bath, kitchen , will add floor recpt at trim by pocket door, ric ok , p/s u/g n ok
ELE06-03961 Electrical Rough-In10/30/200610/31/200610/31/2006 10:35:11 AMAPASS
dave\please call when you are done; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to pour gec, said to call before backfill
ELE06-02747 Final10/31/200610/31/200610/31/2006 10:28:42 AMAPASS
looked at sign, ok to final
ELE06-02746 Final10/31/200610/31/200610/31/2006 10:27:43 AMAPASS
looked at sign, ok to final
ELE06-04031 Temporary Service10/31/200610/31/200610/31/2006 10:25:44 AMPPASS
john; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr to provide abrasion protection for gec and bkr closure plates, t/s o/h n ok
ELE06-04020 Rough-In Permanent Service10/30/200610/31/200610/31/2006 9:30:43 AMAPASS
paula - note: call for access ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith called contr to verify front and back recpt, told need guy kit, call when done, ric ok, p/s o/h n ok
ELE06-03743 Electrical Rough-In10/30/200610/31/200610/31/2006 8:50:42 AMAPART
any questions please call Steve Nuxoll; Phone #: ###-#### Internet Inspection Request from: Jeff Radford mech and control room walls ok to cover, will call back for disc in hall
ELE06-03773 Final10/31/200610/31/200610/31/2006 8:23:09 AMAPART
Phone #: ###-#### Internet Inspection Request from: Clyde Logan called contr, need panel cover, circuit id, switch plate, id isolated gnds, will recall when done