FIR07-00404
| FIR-Aging Inspection | 10/31/2007 | 10/31/2007 | 11/2/2007 4:09:04 PM | | DEFR |
|
|
Under construction.
|
FIR07-00405
| FIR-Aging Inspection | 10/31/2007 | 10/31/2007 | 11/2/2007 4:05:31 PM | | DEFR |
|
|
Under construction.
|
FIR06-00504
| INSP-Conference | 10/26/2007 | 10/31/2007 | 11/1/2007 6:30:27 PM | P | PART |
|
|
Completed preliminary fire pump testing including the required min. manual and automatic starts/stops, churn, rated and peak load testing, and flow testing for comparison to mfg. performance curve data. Generator is not completed to enable testing of the transfer switch at the controler, no fire alarm interconnection or supervision tested at this time due to incomplete FA work.
|
FIR06-00007
| INSP-Final Inspection | 10/30/2007 | 10/31/2007 | 11/1/2007 6:10:21 PM | A | PASS |
|
|
Fire alarm final inspection passed, permit finaled.
|
FIR07-00425
| INSP-Sprinkler Rough-in | 10/30/2007 | 10/31/2007 | 11/1/2007 6:09:23 PM | P | NR |
|
|
Rescheduled per contractor.
|
FIR07-00711
| INSP-Final Inspection | 10/30/2007 | 10/31/2007 | 10/31/2007 4:28:15 PM | A | FAIL |
|
|
Final pending HVAC duct detection.
|
FIR07-00670
| INSP-Final Inspection | 10/29/2007 | 10/31/2007 | 10/31/2007 4:26:36 PM | P | PART |
|
|
Items on correction notice verified for completion, fire alarm permit finaled.
|
FIR06-00579
| INSP-Final Inspection | 10/31/2007 | 10/31/2007 | 10/31/2007 1:27:37 PM | P | PASS |
|
|
FA permit finaled.
|
FIR06-00579
| INSP-Conference | 10/30/2007 | 10/31/2007 | 10/31/2007 1:26:34 PM | A | PASS |
|
|
Fire alarm permit okay for final.
|
BLD07-01859
| FIRE-Final Inspection | 10/30/2007 | 10/31/2007 | 10/31/2007 1:15:36 PM | A | FAIL |
|
|
Exit lights at three locations are not functional, provide directional arrows at exit signs where appropriate, provide exit discharge lighting per IFC requirements.
|
FIR07-00827
| INSP-Sprinkler Rough-in | 10/30/2007 | 10/31/2007 | 10/31/2007 1:07:13 PM | A | PART |
|
|
Clouded area on approved plans is okay for cover at the drop ceilings, noted field modifications in pipe routing are acceptable.
|
FIR07-00702
| INSP-Sprinkler Rough-in | 10/30/2007 | 10/31/2007 | 10/31/2007 1:04:51 PM | A | PART |
|
|
See areas noted on approved plans okay for cover at the hard lids including soffits and restrooms.
|
FIR07-00701
| INSP-Sprinkler Rough-in | 10/30/2007 | 10/31/2007 | 10/31/2007 1:02:59 PM | A | PART |
|
|
OH fire sprinkler system modifications are approved for cover at the drop ceilings, minor field changes are accepted.
|
BLD07-00792
| FIRE-Final Inspection | 10/30/2007 | 10/31/2007 | 10/31/2007 1:01:42 PM | A | PASS |
|
|
Fire life safety inspection passed, seal at one door to be installed prior to structural final.
|
FIR07-00575
| INSP-Sprinkler Rough-in/Hydro | 10/30/2007 | 10/31/2007 | 10/31/2007 1:00:40 PM | A | PART |
|
|
Begin pneumatic testing of the preaction system at 12:00 @ 46psig.
|