Inspections for the day of: Wednesday, October 31, 2007.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00404 FIR-Aging Inspection10/31/200710/31/200711/2/2007 4:09:04 PM DEFR
Under construction.
FIR07-00405 FIR-Aging Inspection10/31/200710/31/200711/2/2007 4:05:31 PM DEFR
Under construction.
FIR06-00504 INSP-Conference10/26/200710/31/200711/1/2007 6:30:27 PMPPART
Completed preliminary fire pump testing including the required min. manual and automatic starts/stops, churn, rated and peak load testing, and flow testing for comparison to mfg. performance curve data. Generator is not completed to enable testing of the transfer switch at the controler, no fire alarm interconnection or supervision tested at this time due to incomplete FA work.
FIR06-00007 INSP-Final Inspection10/30/200710/31/200711/1/2007 6:10:21 PMAPASS
Fire alarm final inspection passed, permit finaled.
FIR07-00425 INSP-Sprinkler Rough-in10/30/200710/31/200711/1/2007 6:09:23 PMPNR
Rescheduled per contractor.
FIR07-00711 INSP-Final Inspection10/30/200710/31/200710/31/2007 4:28:15 PMAFAIL
Final pending HVAC duct detection.
FIR07-00670 INSP-Final Inspection10/29/200710/31/200710/31/2007 4:26:36 PMPPART
Items on correction notice verified for completion, fire alarm permit finaled.
FIR06-00579 INSP-Final Inspection10/31/200710/31/200710/31/2007 1:27:37 PMPPASS
FA permit finaled.
FIR06-00579 INSP-Conference10/30/200710/31/200710/31/2007 1:26:34 PMAPASS
Fire alarm permit okay for final.
BLD07-01859 FIRE-Final Inspection10/30/200710/31/200710/31/2007 1:15:36 PMAFAIL
Exit lights at three locations are not functional, provide directional arrows at exit signs where appropriate, provide exit discharge lighting per IFC requirements.
FIR07-00827 INSP-Sprinkler Rough-in10/30/200710/31/200710/31/2007 1:07:13 PMAPART
Clouded area on approved plans is okay for cover at the drop ceilings, noted field modifications in pipe routing are acceptable.
FIR07-00702 INSP-Sprinkler Rough-in10/30/200710/31/200710/31/2007 1:04:51 PMAPART
See areas noted on approved plans okay for cover at the hard lids including soffits and restrooms.
FIR07-00701 INSP-Sprinkler Rough-in10/30/200710/31/200710/31/2007 1:02:59 PMAPART
OH fire sprinkler system modifications are approved for cover at the drop ceilings, minor field changes are accepted.
BLD07-00792 FIRE-Final Inspection10/30/200710/31/200710/31/2007 1:01:42 PMAPASS
Fire life safety inspection passed, seal at one door to be installed prior to structural final.
FIR07-00575 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 1:00:40 PMAPART
Begin pneumatic testing of the preaction system at 12:00 @ 46psig.