Inspections for the day of: Wednesday, October 31, 2007.
Number of inspections: 22
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00011 INSP-Alarm Testing10/31/200710/31/200711/1/2007 10:16:41 AMPCANC
Overbooked to be rescheduled.
BLD07-00987 FIRE-Final Inspection10/30/200710/31/200710/31/2007 6:31:12 PMAFAIL
Provide approved door hardware including on the sliding door.
FIR07-00671 INSP-Final Inspection10/30/200710/31/200710/31/2007 6:29:03 PMADONE
See mike timmermans notes for items tested.
BLD06-02950 FIRE-Final Inspection10/30/200710/31/200710/31/2007 6:27:22 PMAFAIL
See the job site correction notice for items needing correcting.
FIR07-00878 INSP-Final Inspection10/31/200710/31/200710/31/2007 6:25:47 PMAFAIL
Make modifications to the duct smoke detector mounting, provide additional smoke detector on the north side of the fire door as discussed and change the existing riser from a trouble signal to a fire alarm signal.
FIR07-00477 INSP-Final Inspection10/30/200710/31/200710/31/2007 6:22:55 PMAPASS
permit finaled
BLD06-03284 FIRE-Final Inspection10/30/200710/31/200710/31/2007 6:17:21 PMPPASS
Life safety finaled
BLD07-00986 FIRE-Conference10/30/200710/31/200710/31/2007 6:16:10 PMADONE
I went over life safety requirements with the builder. He stated that he was going to install two vehicle gates. One on the south side of the building and the other on the north. I told him he needs fire dept approval for this. I told him about none hardened locks and the opticom systems.
BLD07-02800 FIRE-Final Inspection10/30/200710/31/200710/31/2007 1:36:53 PMPPART
A temporary occupancy was given until the thumbturn is removed from the main exit, approved hardware is installed on the west exit door and the electrical outlets are covered.
FIR07-00633 FIR-Aging Inspection10/31/200710/31/200710/31/2007 1:02:03 PM NR
work is in progress
FIR07-00461 INSP-Sprinkler Rough-in10/30/200710/31/200710/31/2007 1:00:35 PMAPASS
The underground piping is ok to cover but the installation does not match the plans. Additional fitting have been added as well as additional piping. I'm contacting DeBest Fire about my concerns.
FIR07-00586 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 12:11:41 PMAFAIL
Overhead hydro failed due to loss of pressure and the fdc not being tested.
FIR07-00582 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 12:11:12 PMAFAIL
Overhead hydro failed due to loss of pressure and the fdc not being tested.
FIR07-00585 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 12:10:49 PMAFAIL
Overhead hydro failed due to loss of pressure and the fdc not being tested.
FIR07-00584 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 12:10:07 PMAFAIL
Overhead hydro failed due to loss of pressure and the fdc not being tested.
FIR07-00581 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 12:09:17 PMAFAIL
Overhead hydro failed due to loss of pressure and the fdc not being tested.
FIR07-00583 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 12:08:51 PMAFAIL
Overhead hydro failed due to loss of pressure and the fdc not being tested.
FIR07-00580 INSP-Sprinkler Rough-in/Hydro10/30/200710/31/200710/31/2007 11:48:13 AMAFAIL
Overhead hydro failed due to loss of pressure and the fdc not being tested.
BLD07-02823 FIRE-Final Inspection10/30/200710/31/200710/31/2007 11:46:02 AMAFAIL
The tenant space needs sprinkler work which will require a permit, cover the electrical outlets, provide the usual sticker at the main exit and provide an approved fire extinguisher with tag as discussed.
FIR07-00642 INSP-Final Inspection10/30/200710/31/200710/31/2007 7:24:05 AMAFAIL
401canopies need to be installed in the restrooms where lights are blocking pendant heads. One head needs to be added at a fixture on the sales floor and two heads are located too close to one another at another fixture on the sales floor. Plans need to be resubmitted to the city of boise due to the amount of added heads caused by the fixtures. The scope of work calls for the air compressor to be changed out which has not been done yet.
FIR07-00735 INSP-Sprinkler Rough-in10/30/200710/31/200710/31/2007 7:23:31 AMAFAIL
401canopies need to be installed in the restrooms where lights are blocking pendant heads. One head needs to be added at a fixture on the sales floor and two heads are located too close to one another at another fixture on the sales floor. Plans need to be resubmitted to the city of boise due to the amount of added heads caused by the fixtures. The scope of work calls for the air compressor to be changed out which has not been done yet.
FIR07-00632 FIR-Aging Inspection10/31/200710/31/200710/31/2007 6:19:42 AM NR
work is in progress