BLD08-02224
| FIRE-Final Inspection | 10/30/2008 | 10/31/2008 | 10/31/2008 4:26:24 PM | A | PASS |
|
|
Life safety passed
|
FIR07-01051
| INSP-Sprinkler Rough-in | 10/31/2008 | 10/31/2008 | 10/31/2008 4:14:12 PM | P | PART |
|
|
See the city approved plans for locations where hanger attachments can be covered and sprinkler piping can be covered such as at both pairs of second floor restrooms.
|
FIR08-00689
| INSP-Final Inspection | 10/31/2008 | 10/31/2008 | 10/31/2008 4:09:55 PM | P | PASS |
|
|
Permit finaled
|
FIR08-00402
| INSP-Final Inspection | 10/31/2008 | 10/31/2008 | 10/31/2008 4:07:59 PM | P | PASS |
|
|
permit finaled
|
BLD08-01438
| FIRE-Final Inspection | 10/29/2008 | 10/31/2008 | 10/31/2008 2:37:56 PM | A | PASS |
|
|
Life safety passed.
|
BLD07-02567
| FIRE-Final Inspection | 10/30/2008 | 10/31/2008 | 10/31/2008 1:39:48 PM | A | PASS |
|
|
Life safety passed.
|
FIR08-00595
| INSP-Sprinkler Rough-in/Hydro | 10/29/2008 | 10/31/2008 | 10/31/2008 12:26:25 PM | A | CANC |
|
|
Per Charles the hydro test is to be cancelled.
|
FIR08-00627
| INSP-Sprinkler Rough-in/Hydro | 10/30/2008 | 10/31/2008 | 10/31/2008 12:25:42 PM | A | FAIL |
|
|
The underground hydro test failed.
|
FIR08-00595
| INSP-Sprinkler Rough-in | 10/30/2008 | 10/31/2008 | 10/31/2008 10:19:10 AM | A | PART |
|
|
The southwest canopy can be covered. The east canopy can not be covered due to cpvc piping being installed where as the plans indicate steel piping is to be installed. Plans either need to be resubmitted or piping is to be installed as per the plans. Also the upright sprinkler heads through out the rest of the building have not been installed as per NFPA 13 8.6.5.2.1.6 and exhibit 8.20. The general contractor also stated that he would install insulation in the eaves of the tower located on the southwest corner of the building. This space is considered a combustible concealed space.
|
FIR08-00625
| INSP-Final Inspection | 10/29/2008 | 10/31/2008 | 10/31/2008 10:11:09 AM | A | PASS |
|
|
Permit finaled
|
FIR08-00689
| INSP-Alarm Testing | 10/28/2008 | 10/31/2008 | 10/31/2008 10:08:15 AM | A | PASS |
|
|
Permit finaled
|
FIR08-00710
| INSP-Final Inspection | 10/31/2008 | 10/31/2008 | 10/31/2008 12:00:00 AM | P | PASS |
|
|
Per phone call with Troy ok to pass final inspection
|