Inspections for the day of: Friday, October 31, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD08-02224 FIRE-Final Inspection10/30/200810/31/200810/31/2008 4:26:24 PMAPASS
Life safety passed
FIR07-01051 INSP-Sprinkler Rough-in10/31/200810/31/200810/31/2008 4:14:12 PMPPART
See the city approved plans for locations where hanger attachments can be covered and sprinkler piping can be covered such as at both pairs of second floor restrooms.
FIR08-00689 INSP-Final Inspection10/31/200810/31/200810/31/2008 4:09:55 PMPPASS
Permit finaled
FIR08-00402 INSP-Final Inspection10/31/200810/31/200810/31/2008 4:07:59 PMPPASS
permit finaled
BLD08-01438 FIRE-Final Inspection10/29/200810/31/200810/31/2008 2:37:56 PMAPASS
Life safety passed.
BLD07-02567 FIRE-Final Inspection10/30/200810/31/200810/31/2008 1:39:48 PMAPASS
Life safety passed.
FIR08-00595 INSP-Sprinkler Rough-in/Hydro10/29/200810/31/200810/31/2008 12:26:25 PMACANC
Per Charles the hydro test is to be cancelled.
FIR08-00627 INSP-Sprinkler Rough-in/Hydro10/30/200810/31/200810/31/2008 12:25:42 PMAFAIL
The underground hydro test failed.
FIR08-00595 INSP-Sprinkler Rough-in10/30/200810/31/200810/31/2008 10:19:10 AMAPART
The southwest canopy can be covered. The east canopy can not be covered due to cpvc piping being installed where as the plans indicate steel piping is to be installed. Plans either need to be resubmitted or piping is to be installed as per the plans. Also the upright sprinkler heads through out the rest of the building have not been installed as per NFPA 13 8.6.5.2.1.6 and exhibit 8.20. The general contractor also stated that he would install insulation in the eaves of the tower located on the southwest corner of the building. This space is considered a combustible concealed space.
FIR08-00625 INSP-Final Inspection10/29/200810/31/200810/31/2008 10:11:09 AMAPASS
Permit finaled
FIR08-00689 INSP-Alarm Testing10/28/200810/31/200810/31/2008 10:08:15 AMAPASS
Permit finaled
FIR08-00710 INSP-Final Inspection10/31/200810/31/200810/31/2008 12:00:00 AMPPASS
Per phone call with Troy ok to pass final inspection