Inspections for the day of: Monday, October 31, 2011.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01892 ELE-Aging Inspection10/31/201110/31/201111/3/2011 9:14:53 PM PASS
see final
ELE11-02466 Permanent Service10/31/201110/31/201110/31/2011 1:45:52 PMPPASS
Permanent service, and final.(?)Chris is contact. Thank you Phone #: ###-#### >> Inspection requested via web by Chris Chesnut p/s o/h n ok
ELE11-02465 Conference10/31/201110/31/201110/31/2011 12:55:35 PMPDONE
Michael-Please call prior to inspection Phone #: ###-#### Discussed home owner adding recessed can lighting
ELE11-01846 Final10/31/201110/31/201110/31/2011 12:29:58 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Dan Rohl final ok
ELE11-02244 Electrical Rough-In10/28/201110/31/201110/31/2011 9:45:24 AMAFAIL
Jodi ###-#### NEC 110.3 Remodel cuttin box not installed according to manufactures design, screws though side of box. Nec 300.4(A) Romex shall not be installed less than 1 1/4 from edge of framing member. Device make-ups need to be completed, but devices not installed yet.
ELE11-02444 Final10/28/201110/31/201110/31/2011 9:05:48 AMAFAIL
wired new heat pump, any questions call Clint @ ###-####. Please call Copper @ ###-#### to set time to meet to be let in to house. Phone #: ###-#### >> Inspection requested via web by Andy Rose Outdoor unit requires service outlet. NEC 400.8 (2) Uses not permitted SO cord not permitted to run through walls.
ELE11-01765 Final10/27/201110/31/201110/31/2011 8:30:24 AMAPASS
Dave Phone #: ###-#### final ok
ELE11-01748 Final10/28/201110/31/201110/31/2011 8:20:34 AMAPASS
Everything has been inspected with the exception of can lights. Phone #: ###-#### >> Inspection requested via web by Clint Tate final ok