BLD12-01694
| FIRE-Final Inspection | 10/30/2012 | 10/31/2012 | 10/31/2012 3:47:17 PM | A | CANC |
|
|
Project is not ready for a final inspection due to the ceiling tile not being installed. Contractor and I agreed to reschedule for tomorrow morning.
|
FIR12-00483
| INSP-Sprinkler Rough-in | 10/31/2012 | 10/31/2012 | 10/31/2012 3:45:26 PM | P | PASS |
|
|
See the as-built drawings for additional locations, to the city approved plans, where piping is ok to cover.
|
FIR12-00247
| INSP-Supply line flush | 10/30/2012 | 10/31/2012 | 10/31/2012 3:08:04 PM | A | PASS |
|
|
Underground flush of buildings 8 and 10 passed
|
BLD11-03016
| FIRE-Final Inspection | 10/31/2012 | 10/31/2012 | 10/31/2012 3:07:29 PM | P | FAIL |
|
|
Provide final approval of the underground fuel storage tanks through the Boise Fire Dept., replace all of the painted sprinkler uprights in the wash bay (24 of them) and remove the existing horizontal sidewalls that were left when the overhead doors were removed (they are too far from the deck), reverse door hardware at the passage between the washbay and the shop, provide signage per fire review note #22 at the emergency stop button, provide signage for "partially sprinkler building and zone map" at the fire dept. connection as discussed. Two emergency lights repaired as I waited. Emergency stop of gas pump passed, fire extinguisher at pump as well as signage. Per Romeo Gervais final life safety not to be given until the fire dept. sign off on the fuel tanks. Per Scott Arellano the new additions are not required to have the existing fire protection extended into them.
|
FIR11-00624
| INSP-Final Inspection | 10/30/2012 | 10/31/2012 | 10/31/2012 11:05:03 AM | A | PASS |
|
|
Permit finaled
|
FIR12-00247
| INSP-Sprinkler Rough-in | 10/30/2012 | 10/31/2012 | 10/31/2012 12:00:00 AM | A | CANC |
|
|
Underground fluch - Jonathan Phone #: ###-####///scheduled wrong type
|
BLD12-02782
| FIRE-Final Inspection | 10/31/2012 | 10/31/2012 | 10/31/2012 12:00:00 AM | P | CANC |
|
|
JED Phone #: ###-#### CARISSA called to canc this inspection ///dld
|