Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00579 INSP-Sprinkler Rough-in10/31/201310/31/201311/1/2013 6:50:45 AMPPART
Rough-in inspection for the 3rd floor unit rooms only- Identified concealed combustible spaces at some areas in need of coverage or meet allowable conditions per NFPA 13. Clarify if space between ceiling and deck above the kitchens will be sheetrocked. Plan modification to include deleted pendents at the end of lines in some units. Branchlines and head spacing okayed.
FIR13-00440 INSP-Sprinkler Rough-in10/31/201310/31/201311/1/2013 6:42:30 AMPPART
Rough-in for the 7th floor completed- okay to cover areas with sheetrock ceilings at the RR's and hallway. Missing coverage at one closet per plan- ref. dated annotation. Also noted lacking coverage (existing conditions) at the elevator machine room, penthouse, and some areas between floor levels of the basement, 1st and 2nd.
BLD13-01618 FIRE-Final Inspection10/31/201310/31/201311/1/2013 6:34:05 AMPNR
Final pending project related fire sprinkler permit work.
FIR06-00798 INSP-Final Inspection10/29/201310/31/201311/1/2013 6:32:58 AMAPASS
Fire alarm work passed functional testing. Permit final approved.
BLD13-03009 FIRE-Final Inspection10/30/201310/31/201310/31/2013 12:00:00 AMPPASS