Inspections for the day of: Monday, October 31, 2016.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorKatie Marron
TitleFIRE INSPECTOR
Phone #395-7809
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00088 INSP-Sprinkler Rough-in10/28/201610/31/201610/31/2016 10:32:32 AMADONE
Third Floor Soffits inspected (except community space).
- Soffit over 30' requires a sprinkler under in living room unit 304
-Unit 302 bedroom has sprinkler installed under soffit. Contractor to verify one is not required in ceiling pocket (ie meets exceptions of 8.10.8.2)
BLD14-02156 FIRE-Final Inspection10/28/201610/31/201610/31/2016 8:45:04 AMAPASS
No inspection required. Foundation permit. No changes to FD Access or hydrants.
BLD14-02889 FIRE-Final Inspection10/28/201610/31/201610/31/2016 8:43:31 AMACANC
No inspection completed. Waiting to do in conjunction with Fire Alarm Final.
BLD16-01108 FIRE-Conference10/31/201610/31/201610/31/2016 12:00:00 AMPDONE
Scott spoke with Chad and with knox box on order a TCO is authorized pending satisfactory inspection of remaining requirements.