Inspections for the day of: Tuesday, October 31, 2017.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorMark Moncarr
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-02957 Electrical Rough-In10/31/201710/31/201710/31/2017 1:50:14 PMPPASS
Inspect soffit lighting at main entrance for cover. Phone #: ###-#### Inspection requested via web by Chase Sessions Ok cover cans outer entry soffit.
ELE17-03649 Conference10/31/201710/31/201710/31/2017 1:11:05 PMPDONE
Spoke with Brent about project. We discussed making previous electrical work safe, and that any wall that is open needs to be brought up to code.
ELE17-03586 Final10/31/201710/31/201710/31/2017 12:39:08 PMPPASS
Bonding Phone #: ###-#### Inspection requested via web by Eric White Ok cover. Perimeter bond at 4" depth. Pockets for diving board on W side, ladder on S side and handrail on E side all bonded with UL listed PVC bonding pockets.
ELE17-03673 Electrical Rough-In10/31/201710/31/201710/31/2017 12:23:57 PMPPASS
Phone #: ###-#### Inspection requested via web by steve cooper p/s u/g n ok
ELE17-03653 Electrical Rough-In10/31/201710/31/201710/31/2017 12:21:33 PMPPASS
Uffer covered Phone #: ###-#### Inspection requested via web by Emmet Bushman Ok cover. GEC encased in 2-3" of concrete a long footing.
ELE14-00774 Final10/30/201710/31/201710/31/2017 12:11:49 PMPNR
Please call Alisha 20-30 min prior to inspection so she can let you in. Alisha''s cell no. is ###-####. Phone #: ###-#### Inspection requested via web by Shawna Gates
ELE17-03647 Final10/30/201710/31/201710/31/2017 10:42:09 AMAPASS
steam shower Phone #: ###-#### Inspection requested via web by PAT MILLER Ok final. Unit pulls32a, breakered at 40a with #6 THHN.
ELE17-03647 Electrical Rough-In10/30/201710/31/201710/31/2017 10:41:02 AMAPASS
steam shower Phone #: ###-#### Inspection requested via web by PAT MILLER Ok cover.
ELE17-02852 Final10/30/201710/31/201710/31/2017 9:47:50 AMAPASS
She will be there after 9 am Her name is Sarah. any questions please give me a call. Thank you. Phone #: ###-#### Inspection requested via web by David Kubik Ok final.
ELE17-03589 Permanent Service10/26/201710/31/201710/31/2017 9:27:49 AMPPASS
Contact: Jason Noble Phone #: ###-#### Inspection requested via web by Deb Gooden p/s o/h n ok. Talked to troubleman on site. They wanted approval to energize service so long as the contractor safes off main breaker in all in one on detached garage until house panel is completed.
ELE17-01464 Final10/30/201710/31/201710/31/2017 9:13:54 AMAPASS
Phone #: ###-#### Inspection requested via web by Jerry Moore Ok final.
ELE17-03423 Electrical Rough-In10/30/201710/31/201710/31/2017 8:57:50 AMAPASS
Call Brad 1 hour in advance. Phone #: ###-#### Inspection requested via web by Christian Kilpatrick Ok cover. All same components used, all are UL listed.
ELE13-03342 ELE-Aging Inspection10/31/201710/31/201710/31/2017 7:35:50 AM DONE
Please call with progress on job.
ELE15-00793 Final10/27/201710/31/201710/30/2017 1:17:58 PMAPASS
Aging Phone #: ###-#### Inspection requested via web by Steve VanWinkle Ok final. All items UL listed. Talked to Steve, disconnect located on power supply in ceiling.
ELE17-03653 Electrical Rough-In10/30/201710/31/201710/30/2017 1:01:05 PMAPASS
ground wire uffer inspection Phone #: ###-#### Inspection requested via web by Emmet Bushman Ok cover. #4 bare in 20' run within a few inches of 30".