BLD06-02324 FIRE-Final Inspection10/30/201710/31/201710/31/2017 3:25:33 PMAFAIL
Not quite ready for temp. I need the panic hardware installed in the north stairwell. Today we also verified the smoke alarms were functional in Suites 103, 104, 105, 106, 203, 204, 205, 206 and 302
FIR17-00403 INSP-Final Inspection10/30/201710/31/201710/31/2017 3:18:44 PMPCANC
Canceled due to time constraints.

Dave Phone #: ###-####
FIR16-00284 INSP-Final Inspection10/31/201710/31/201710/31/2017 3:18:11 PMPFAIL
Provide minor corrections as discussed with the pipe clearance and pipe straps. Need test papers
FIR16-00446 INSP-Final Inspection10/30/201710/31/201710/31/2017 3:12:47 PMAPASS
permit finaled
FIR17-00611 INSP-Sprinkler Rough-in10/30/201710/31/201710/31/2017 1:58:50 PMPPASS
Rough-in passed. Piping can be covered. One pendant located in the Dining Area at the Kitchen wall needs relocated from wall and will be checked at the final.
BLD05-02431 FIRE-Final Inspection10/30/201710/31/201710/31/2017 1:06:41 PMAFAIL
The new fire extinguishers, although new, still require inspection tags and the previous corrections required exit discharge lighting that is not installed
BLD16-04253 FIRE-Final Inspection10/30/201710/31/201710/31/2017 12:33:01 PMAPASS
Life safety passed. Contractor provided documentation that the thumbturn deadbolt hardware met ADA
FIR17-00360 INSP-Final Inspection10/30/201710/31/201710/31/2017 12:32:09 PMAPASS
Permit finaled
BLD16-04117 FIRE-Final Inspection10/30/201710/31/201710/31/2017 12:18:18 PMAPASS
Life safety passed. The structural inspector verified the combustible concealed space is filled with insulation as per revious entry and the exterior is non-combustible so no sprinklers required per NFPA13 8.15
FIR17-00433 INSP-Sprinkler Rough-in10/30/201710/31/201710/31/2017 12:01:08 PMPCANC
Contact Scott Powada - ###-#### 30 Min Prior to RTC insp Start please

Thank YOU Phone #: ###-#### >> Inspection requested via web by Teri Cruickshank Inspection cancelled from web by: Teri Cruickshank
FIR17-00601 INSP-Final Inspection10/30/201710/31/201710/31/2017 9:08:54 AMACANC
Brandon Phone #: ###-####
FIR17-00602 INSP-Final Inspection10/30/201710/31/201710/31/2017 9:08:15 AMAFAIL
Not ready for inspection. No city approved plans on site. Agreed to reschedule for thursday or friday when kids are out of school

Brandon Phone #: ###-####