Inspections for the day of: Wednesday, October 31, 2018.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE18-03802 Electrical Rough-In10/31/201810/31/201810/31/2018 2:19:59 PMPPART
Randy. Phone #: ###-#### Inspection requested via web by Sean DeLacy
From center to north interior wall rough in ok cover
ELE18-04112 Final10/31/201810/31/201810/31/2018 1:59:16 PMPPASS
Wired low volt lights around ledge. Photos will be sent. Phone #: ###-#### Inspection requested via web by Greg Idsinga
Final ok
ELE18-04112 Electrical Rough-In10/31/201810/31/201810/31/2018 1:06:11 PMPPASS
Wired low volt lights around ledge. Photos will be sent. Phone #: ###-#### Inspection requested via web by Greg Idsinga
All wiring surface mount conduit. LED ribbon lighting listing comfirmed. Rough in ok cover
ELE18-03890 Electrical Rough-In10/30/201810/31/201810/31/2018 11:40:48 AMAPASS
Please call Lynn prior to arrival at ###-#### or Dan at ###-####. Phone #: ###-#### Inspection requested via web by Lynn Proctor
Badge required to access elevator. call Travis ###-#### foreman on site for access.
Discussed access shall be provided for electrical box at HVAC equipment located in ceiling areas
Wall rough in on entire floor rough in ok cover
ELE17-02862 Final10/29/201810/31/201810/31/2018 11:37:44 AMAPART
Finals for units on 5th floor ,hallway and storage rooms, Units 502 thru 519 call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
314.20- Interior of boxes shall not be exposed to combustible materials. 504 disposal located pert behind cabinet divider. 506 microwave receptacle located part behind divider.
110.3- All siring shall be terminated as per drawing and manufacturers instructions. 505 3 bed receptacles not working, 508,510,513 all have 2 single pole switches controlling living room lights, 511 open ground in living room receptacle.
502, 503, 507, 509, 512, 514, 515, 516, 517, 518, 519 rooms only TCO ok