ELE19-01489
| Permanent Service | 10/31/2019 | 10/31/2019 | 10/31/2019 2:43:56 PM | P | CANC |
|
|
Toby is the contact Phone #: ###-#### Inspection requested via web by Buster Bowen As per phone call to 363 need to cancel and will recall Tuesday
|
ELE19-03174
| Final | 10/30/2019 | 10/31/2019 | 10/31/2019 2:16:54 PM | P | FAIL |
|
|
Inspect for TCO. Mike Hastings ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud 210.8(B)- All receptacles located in a commercial kitchen up to 50 amp single phase and 100 amp 3 phase 150 volts or less to ground shall have GFCI protection. 2-pole 20 for small oven. 408.4- Circuit directory shall be placed in each panel. 422.30- A disconnecting means shall be provided for all hard wired appliances. 9 ish needed.
|
ELE19-02744
| Final | 10/30/2019 | 10/31/2019 | 10/31/2019 11:56:25 AM | A | PASS |
|
|
Please call if you need access - Todd ###-#### Phone #: ###-#### Inspection requested via web by Kendra Lanham Final ok
|
ELE19-03563
| Final | 10/30/2019 | 10/31/2019 | 10/31/2019 11:24:18 AM | A | PASS |
|
|
Patrick is our contact Phone #: ###-#### Inspection requested via web by A.M.E. Office Final ok
|
ELE19-01406
| Electrical Rough-In | 10/30/2019 | 10/31/2019 | 10/31/2019 11:22:09 AM | A | PASS |
|
|
Contact John for westside site pole bases. Phone #: ###-#### Inspection requested via web by Tom Betty 2 S W pole bases rough in ok cover
|
ELE19-04143
| Rough-In Permanent Service | 10/30/2019 | 10/31/2019 | 10/31/2019 10:40:07 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Alan Lusk Rough in ok cover p/s u/g n ok
|
ELE19-03896
| Rough-In Permanent Service | 10/30/2019 | 10/31/2019 | 10/31/2019 10:01:47 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn Rough in ok cover p/s o/h n ok
|
ELE19-04188
| Rough-In Permanent Service | 10/30/2019 | 10/31/2019 | 10/31/2019 9:35:57 AM | A | PASS |
|
|
Ben Hale is the homeowner and works 15 mis from home, can you give him the heads up when you''re 20-30 min out, his number is ###-####. We are moving service from one side of the house to the other and need inspection prior to Idaho Power to swing to ne all in one, panel in garage will become a sub and will need inspected @ final after new power swing. Thanks, Greg. Phone #: ###-#### Inspection requested via web by Greg Traudt Rough in to repair patches in down basement rough in ok cover. p/s u/g n ok
|