Inspections for the day of: Thursday, October 31, 2019.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Reynolds
TitleMEC INSPECTOR
Phone #208-803-2395
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC19-03531 Final10/31/201910/31/201910/31/2019 3:27:43 PMPPASS
garage #1957 lockbox: BMW Phone #: ###-#### Inspection requested via web by Debbie Marino
- final ok
MEC19-03529 Final10/31/201910/31/201910/31/2019 3:27:31 PMPPASS
garage 1957 lockbox : BMW Phone #: ###-#### Inspection requested via web by Debbie Marino
- final ok
MEC19-04450 Final10/29/201910/31/201910/31/2019 3:05:54 PMPFAIL
replaced ac and furnace Phone #: ###-#### Inspection requested via web by John Eastman
- gas line needs sediment trap at furnace
- A/C needs locking caps installed on service ports
MEC19-04853 Final10/28/201910/31/201910/31/2019 1:05:22 PMPPASS
Please call John to ensure install is complete. thank you! ###-#### Phone #: ###-#### Inspection requested via web by Rick Borg
- final ok
MEC19-04907 Final10/31/201910/31/201910/31/2019 12:56:13 PMPCANC
Please call Tony, tech on site, at number provided to ensure job is ready. Same day install. Flue Pressure test will also be performed. Requested separately. If you have any issues, please call Alyssa at ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Alyssa Cromwell Inspection cancelled from web by: Alyssa Cromwell
MEC19-04808 Pressure Test10/30/201910/31/201910/31/2019 11:54:20 AMAPASS
Inspection requested via web by Andrea Creek
- 20lb gas pressure test in mech room ok
MEC19-04908 Rough-in10/30/201910/31/201910/31/2019 11:53:38 AMAFAIL
Cover Inspection for Building B Unit 3. Please contact Mark Prior to coming out. ###-#### Phone #: ###-#### Inspection requested via web by Commercial Coordinator

- duct seal ok on middle unit
- exhaust termination on 1st floor is within 3' of window and front door of next unit
MEC19-04479 Pressure Test10/29/201910/31/201910/31/2019 10:13:24 AMAPASS
Brad Phone #: ###-####
- 20lb gas pressure test ok
- tagged meter location
MEC19-04907 Final10/30/201910/31/201910/31/2019 9:27:23 AMACANC
Please call Tony, tech on site, at number provided to ensure job is ready. Same day install. Flue Pressure test will also be performed. Requested separately. If you have any issues, please call Alyssa at ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Alyssa Cromwell
- scheduled inspection for this afternoon per Tony
MEC19-04907 Pressure Test10/30/201910/31/201910/31/2019 9:26:32 AMACANC
Please call Tony, tech on site, at number provided to ensure job is ready. Same day install. Final inspection will also be performed. Requested separately. If you have any issues, please call Alyssa at ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Alyssa Cromwell
- no need for 5lb flue pressure test
MEC19-01466 Mec-Aging Inspection10/31/201910/31/201910/31/2019 8:25:09 AM FAIL
Permit has not been active since 4/11/19 when it was issued. Schedule inspection with homeowner if work is finished. Permit will expired at the next aging inspection if not active.
MEC19-04898 Rough-in10/30/201910/31/201910/30/2019 8:10:46 PMPCANC
Thank you Phone #: ###-#### >> Inspection requested via web by Aaron Johns Inspection cancelled from web by: Aaron Johns