Inspections for the day of: Tuesday, October 4, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03297 Electrical Rough-In10/4/200510/4/200510/4/2005 3:39:26 PMPPART
loren; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles wall new office
ELE05-03013 Electrical Rough-In10/4/200510/4/200510/4/2005 2:37:19 PMPPART
dan Note: cover; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles
walls and all ceilings except grid ceilings
ELE05-02086 Final10/4/200510/4/200510/4/2005 1:45:13 PMPNR
TEMPORARY OCCUPANCY BECAUSE WE HAVE NOT POURED POLE BASES CAUSE CONCRETE SHORTAGE; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen needs to remove all the child proof covers from recepts called
ELE05-03616 Electrical Rough-In10/3/200510/4/200510/4/2005 1:12:16 PMPPASS
please call prior to inspection so he can give you access///tim ###-#### ok
ELE05-03603 Final10/3/200510/4/200510/4/2005 10:56:19 AMANR
Internet Inspection Request from: Steve Syltie
ELE05-03600 Final10/3/200510/4/200510/4/2005 10:56:06 AMANR
Internet Inspection Request from: Steve Syltie
ELE05-03602 Final10/3/200510/4/200510/4/2005 10:55:50 AMANR
Internet Inspection Request from: Steve Syltie
ELE05-03604 Permanent Service10/4/200510/4/200510/4/2005 10:03:22 AMAFAIL
Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack cor. posted called,250.30(A)(7)&250.64(C) electrode from 120/240 panel shall be continuous, 250.56 test or 2 grd rods required, 250.29 needs bond bushung at 120/240 panel
ELE05-03312 Electrical Rough-In10/3/200510/4/200510/4/2005 8:50:00 AMAPART
ceiling insp.///wayne; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa 2 offices ok only big rm not ready too many violations strap flex seal KOs support boxes,cables, called
ELE05-02414 Final10/3/200510/4/200510/4/2005 8:23:58 AMAPASS
Please contact Dennis at ###-#### 30 minutes prior to inspection to gain entry.; Phone #: ###-#### Internet Inspection Request from: Gary Gettman ok
ELE05-02655 Electrical Rough-In10/4/200510/4/200510/4/2005 12:00:00 AMPPART
emergency and outside lights ok
ELE05-02516 DOC - Permit Finaled10/4/200510/4/200510/4/2005 12:00:00 AMPPASS