Inspections for the day of: Tuesday, October 4, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02787 Final10/4/200510/4/200510/4/2005 4:43:38 PMPPASS
Charlie Internet Inspection Request from: Melyne Davis ok to final
ELE05-02873 Final10/4/200510/4/200510/4/2005 4:42:52 PMPPASS
Charlie Internet Inspection Request from: Melyne Davis called contr to tighten rear outside recpt cover, ok to final
ELE05-03533 Electrical Rough-In10/4/200510/4/200510/4/2005 2:59:34 PMPPART
underground insp///mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa south part of lot ok to cover u/g only
ELE05-03583 Temporary Service10/4/200510/4/200510/4/2005 2:22:23 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Joe Thomas called contr, left message, left correction notice, fee due for re-inspection, 250.52(A)(5) rod electrodes shall be not less than 8' in length, 250.56 single electrode shall be augmented by one additional electrode, 312.5 conductors entering enclosures shall be protected from abrasion
ELE05-03485 Rough-In Permanent Service9/30/200510/4/200510/4/2005 1:46:50 PMAPASS
Scheduled by a contractor via Hello! on 9/30/2005 at 4:43:42 PM. Contact: ###-####. ric ok, p/s u/g n ok
ELE05-03429 Final10/3/200510/4/200510/4/2005 1:04:41 PMPNR
paul; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, 410.30(C) cord conn fixtures shall be terminated in gnd type plug, 408.4 panel schedule shall be done, 110.3(A) recpt shall not have open neutral,358.30(A),(B) emt shall be strapped within 3' and every 10'
ELE05-03601 Final10/3/200510/4/200510/4/2005 11:56:45 AMANR
Internet Inspection Request from: Steve Syltie no access, no panel sched
ELE05-03615 Electrical Rough-In10/3/200510/4/200510/4/2005 9:56:03 AMAPASS
###-#### doug called cntr to separate lv wiring from line volt, add np. ric ok
ELE05-03614 Temporary Service10/3/200510/4/200510/4/2005 8:44:05 AMAPASS
darrell ###-#### t/s u/g n ok
ELE05-03592 Temporary Service10/3/200510/4/200510/4/2005 8:36:27 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Clyde Logan called, left message to fix abrasion prot for gec. t/s u/g n ok
ELE05-03522 Electrical Rough-In10/4/200510/4/200510/4/2005 8:03:18 AMAPASS
Scheduled by a contractor via Hello! on 10/4/2005 at 7:08:07 AM. Contact: ###-####. rooms anop ok to cover walls only