BLD06-00376
| FIRE-Final Inspection | 10/4/2006 | 10/4/2006 | 10/5/2006 11:36:28 AM | P | FAIL |
|
|
duct smoke detectors need to be relocated closer to the deck and the exit sign at the main exit needs repaired.
|
FIR06-00516
| INSP-Final Inspection | 10/4/2006 | 10/4/2006 | 10/5/2006 9:20:35 AM | P | CANC |
|
|
waiting for Forrest to verify as-builts or for the contractor to walk me throught the system to verify it myself
|
MIS06-00080
| FIR-Final | 10/4/2006 | 10/4/2006 | 10/4/2006 3:46:18 PM | P | PASS |
|
|
Life safety finaled
|
FIR06-00640
| INSP-Sprinkler Rough-in | 10/4/2006 | 10/4/2006 | 10/4/2006 3:45:58 PM | P | PASS |
|
|
Sprinkler piping is ok to cover
|
BLD06-02188
| FIRE-Final Inspection | 10/4/2006 | 10/4/2006 | 10/4/2006 2:25:14 PM | P | FAIL |
|
|
provide approved hardware on the two east facing exit doors
|
BLD05-00200
| FIRE-Final Inspection | 10/4/2006 | 10/4/2006 | 10/4/2006 1:06:45 PM | P | PASS |
|
|
life safety finaled
|
FIR06-00685
| INSP-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 1:03:57 PM | P | CANC |
|
|
Waiting on fire alarm
|
FIR05-00368
| INSP-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 1:03:33 PM | P | CANC |
|
|
Waiting on fire alarm
|
FIR06-00669
| INSP-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 1:01:22 PM | P | CANC |
|
|
missing relays for hvac shutdown
|
FIR06-00627
| INSP-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 1:00:51 PM | P | CANC |
|
|
missing relays for hvac shutdown
|
BLD06-00830
| FIRE-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 12:38:21 PM | P | FAIL |
|
|
Need fire alarm permit finaled and one emergency light provided that was not installled as per the plans and one existing exit sign has a burnt out buld. These items are marked on the city approved plans.
|
FIR06-00231
| INSP-Alarm Testing | 10/3/2006 | 10/4/2006 | 10/4/2006 11:59:49 AM | A | FAIL |
|
|
Provide a/v devices as marked on the as-built plans in the two restrooms and the storage room.
|
BLD06-02560
| FIRE-Final Inspection | 10/4/2006 | 10/4/2006 | 10/4/2006 11:46:17 AM | P | PASS |
|
|
Life safety finaled
|
FIR05-00403
| INSP-Conference | 10/3/2006 | 10/4/2006 | 10/4/2006 11:18:39 AM | A | FAIL |
|
|
Insulation was not done yet.
|
FIR06-00727
| INSP-Supply line flush | 10/2/2006 | 10/4/2006 | 10/4/2006 9:55:47 AM | A | PART |
|
|
Inspection was for cover of the underground pipe. Piping is ok to cover from the building stub-in up to the last 45 elbow. The PIV and the connection to united water has not been completed yet.
|
BLD06-00777
| FIRE-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 9:54:37 AM | A | PASS |
|
|
Life safety finaled
|
BLD06-01623
| FIRE-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 9:23:40 AM | A | PASS |
|
|
Life safety finaled
|
FIR06-00735
| INSP-Final Inspection | 10/3/2006 | 10/4/2006 | 10/4/2006 9:23:10 AM | A | PASS |
|
|
permit finaled
|
BLD06-01741
| FIRE-Final Inspection | 10/3/2006 | 10/4/2006 | 10/3/2006 2:55:40 PM | A | PASS |
|
|
Life safety finaled
|