Inspections for the day of: Thursday, October 4, 2007.
Number of inspections: 19
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-03353 Rough-In Permanent Service10/4/200710/4/200710/4/2007 3:44:52 PMPPART
Office area rough inspection. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson no p/s r/i ok walls and hard ceilings ok fire job
ELE07-02560 Final10/4/200710/4/200710/4/2007 3:15:51 PMPFAIL
Scheduled by a contractor via Hello! on 10/4/2007 at 9:17:46 AM. Contact: ###-####. corr. called 210.52(A) needs recept east wall fam. rm. right of builtin cabinet, within 6ft outlet for TV set too hign to serve wall space it's over 51/2 ft, 408.4 panel schedule be specific purpose and use all breakers, 210.8 all new outlets in garage need gfci
ELE07-02938 Electrical Rough-In10/4/200710/4/200710/4/2007 2:37:40 PMPPART
lloyd - grid ceiling cover Phone #: ###-####
ok
ELE07-03085 Electrical Rough-In10/4/200710/4/200710/4/2007 2:07:53 PMPPASS
Scheduled by a contractor via Hello! on 10/4/2007 at 10:20:33 AM. Contact: ###-####. u/g house to garage ok
ELE07-03085 Permanent Service10/4/200710/4/200710/4/2007 2:05:35 PMPCANC
Scheduled by a contractor via Hello! on 10/4/2007 at 10:20:33 AM. Contact: ###-####. see added r/i
ELE07-03084 Permanent Service10/4/200710/4/200710/4/2007 2:04:17 PMPCANC
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:57 AM. Contact: ###-####. see added r/i
ELE07-03084 Electrical Rough-In10/4/200710/4/200710/4/2007 2:04:03 PMPPASS
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:57 AM. Contact: ###-####. u/g house to garage ok
ELE07-03083 Permanent Service10/4/200710/4/200710/4/2007 2:03:23 PMPCANC
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:17 AM. Contact: ###-####. see add r/i
ELE07-03083 Electrical Rough-In10/4/200710/4/200710/4/2007 2:03:02 PMPPASS
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:17 AM. Contact: ###-####. u/g from house to garage ok
ELE07-03427 Conference10/4/200710/4/200710/4/2007 1:06:38 PMPDONE
###-####--jenny homeowner for elec-call 1st before insp talked with owner told her whats required and what to watch out for, and call if any questions
ELE07-03424 Electrical Rough-In10/4/200710/4/200710/4/2007 12:48:44 PMPPART
lloyd - underground trench Phone #: ###-#### all u/g ok
ELE07-03425 Temporary Service10/4/200710/4/200710/4/2007 11:15:06 AMPPASS
Darryn Phone #: ###-#### t/s u/g new ok
ELE06-02729 Final10/3/200710/4/200710/4/2007 10:56:54 AMAFAIL
lloyd Phone #: ###-#### 210.8 needs gfci all recepts garage, shop area, 334.15 protect horizontally ran cables in stud upstairs storage area, 406.8 needs inuse cover
ELE07-03141 Final10/3/200710/4/200710/4/2007 10:29:50 AMAPASS
dave Phone #: ###-#### ok card signed
ELE07-03021 Final10/3/200710/4/200710/4/2007 10:14:52 AMAPASS
trent Phone #: ###-#### ok card signed
ELE07-03413 Electrical Rough-In10/3/200710/4/200710/4/2007 9:47:10 AMAPART
john campbell- ###-#### soffit walls and u/g
ELE07-03416 Temporary Service10/3/200710/4/200710/4/2007 9:28:15 AMAFAIL
Olga Phone #: ###-#### called left message fee due, 400.8(1) cord used as fixed wiring, 408.41 neutrals doubled up under terminals, 110.12(C) clean dirt from t/s 230.24(B)(1) needs 10ft from drip loop to grade level, 312.5 conn for GEC, 110.3(A) tighten screws and fittings, 310.16 #12 protected by 30 amp wire at 2 pole breaker
ELE07-02547 Electrical Rough-In10/4/200710/4/200710/4/2007 8:25:47 AMAPART
Contact is Perry. Please inspect U/G to freezer cases on Main Sales floor. Phone #: ###-#### Internet Inspection Request from: David Bonner u/g anop
ELE07-03282 Electrical Rough-In10/3/200710/4/200710/4/2007 7:58:48 AMAPART
Interior Rough In. Please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson walls ok called contr, 410.30(C) cord for high bay fixtures shall terimnate in cord cap and recept, or use MC or flex