ELE07-03353
| Rough-In Permanent Service | 10/4/2007 | 10/4/2007 | 10/4/2007 3:44:52 PM | P | PART |
|
|
Office area rough inspection. Thank you!! Phone #: ###-#### Internet Inspection Request from: Tracy Robertson no p/s r/i ok walls and hard ceilings ok fire job
|
ELE07-02560
| Final | 10/4/2007 | 10/4/2007 | 10/4/2007 3:15:51 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 9:17:46 AM. Contact: ###-####. corr. called 210.52(A) needs recept east wall fam. rm. right of builtin cabinet, within 6ft outlet for TV set too hign to serve wall space it's over 51/2 ft, 408.4 panel schedule be specific purpose and use all breakers, 210.8 all new outlets in garage need gfci
|
ELE07-02938
| Electrical Rough-In | 10/4/2007 | 10/4/2007 | 10/4/2007 2:37:40 PM | P | PART |
|
|
lloyd - grid ceiling cover Phone #: ###-#### ok
|
ELE07-03085
| Electrical Rough-In | 10/4/2007 | 10/4/2007 | 10/4/2007 2:07:53 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 10:20:33 AM. Contact: ###-####. u/g house to garage ok
|
ELE07-03085
| Permanent Service | 10/4/2007 | 10/4/2007 | 10/4/2007 2:05:35 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 10:20:33 AM. Contact: ###-####. see added r/i
|
ELE07-03084
| Permanent Service | 10/4/2007 | 10/4/2007 | 10/4/2007 2:04:17 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:57 AM. Contact: ###-####. see added r/i
|
ELE07-03084
| Electrical Rough-In | 10/4/2007 | 10/4/2007 | 10/4/2007 2:04:03 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:57 AM. Contact: ###-####. u/g house to garage ok
|
ELE07-03083
| Permanent Service | 10/4/2007 | 10/4/2007 | 10/4/2007 2:03:23 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:17 AM. Contact: ###-####. see add r/i
|
ELE07-03083
| Electrical Rough-In | 10/4/2007 | 10/4/2007 | 10/4/2007 2:03:02 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/4/2007 at 10:19:17 AM. Contact: ###-####. u/g from house to garage ok
|
ELE07-03427
| Conference | 10/4/2007 | 10/4/2007 | 10/4/2007 1:06:38 PM | P | DONE |
|
|
###-####--jenny homeowner for elec-call 1st before insp talked with owner told her whats required and what to watch out for, and call if any questions
|
ELE07-03424
| Electrical Rough-In | 10/4/2007 | 10/4/2007 | 10/4/2007 12:48:44 PM | P | PART |
|
|
lloyd - underground trench Phone #: ###-#### all u/g ok
|
ELE07-03425
| Temporary Service | 10/4/2007 | 10/4/2007 | 10/4/2007 11:15:06 AM | P | PASS |
|
|
Darryn Phone #: ###-#### t/s u/g new ok
|
ELE06-02729
| Final | 10/3/2007 | 10/4/2007 | 10/4/2007 10:56:54 AM | A | FAIL |
|
|
lloyd Phone #: ###-#### 210.8 needs gfci all recepts garage, shop area, 334.15 protect horizontally ran cables in stud upstairs storage area, 406.8 needs inuse cover
|
ELE07-03141
| Final | 10/3/2007 | 10/4/2007 | 10/4/2007 10:29:50 AM | A | PASS |
|
|
dave Phone #: ###-#### ok card signed
|
ELE07-03021
| Final | 10/3/2007 | 10/4/2007 | 10/4/2007 10:14:52 AM | A | PASS |
|
|
trent Phone #: ###-#### ok card signed
|
ELE07-03413
| Electrical Rough-In | 10/3/2007 | 10/4/2007 | 10/4/2007 9:47:10 AM | A | PART |
|
|
john campbell- ###-#### soffit walls and u/g
|
ELE07-03416
| Temporary Service | 10/3/2007 | 10/4/2007 | 10/4/2007 9:28:15 AM | A | FAIL |
|
|
Olga Phone #: ###-#### called left message fee due, 400.8(1) cord used as fixed wiring, 408.41 neutrals doubled up under terminals, 110.12(C) clean dirt from t/s 230.24(B)(1) needs 10ft from drip loop to grade level, 312.5 conn for GEC, 110.3(A) tighten screws and fittings, 310.16 #12 protected by 30 amp wire at 2 pole breaker
|
ELE07-02547
| Electrical Rough-In | 10/4/2007 | 10/4/2007 | 10/4/2007 8:25:47 AM | A | PART |
|
|
Contact is Perry. Please inspect U/G to freezer cases on Main Sales floor. Phone #: ###-#### Internet Inspection Request from: David Bonner u/g anop
|
ELE07-03282
| Electrical Rough-In | 10/3/2007 | 10/4/2007 | 10/4/2007 7:58:48 AM | A | PART |
|
|
Interior Rough In. Please call Steve Ruter Phone #: ###-#### Internet Inspection Request from: Kristopher Wilson walls ok called contr, 410.30(C) cord for high bay fixtures shall terimnate in cord cap and recept, or use MC or flex
|