FIR07-00316
| INSP-Final Inspection | 10/1/2007 | 10/4/2007 | 10/5/2007 10:37:18 AM | P | CANC |
|
|
bill Phone #: ###-#### Incorrect permit number called in, was intended for the project related fire alarm permit.
|
FIR07-00619
| INSP-Final Inspection | 10/4/2007 | 10/4/2007 | 10/5/2007 10:35:11 AM | P | FAIL |
|
|
Added upright heads will need to be shown on approved resubmittals including revised hydraulic calculations, also need to provide coverage below the overhead doors, forward flow has not been completed, insulation at the deck is not finished at some areas, may need high temp heads above unit heaters.
|
FIR07-00765
| INSP-Sprinkler Rough-in/Hydro | 10/3/2007 | 10/4/2007 | 10/5/2007 10:31:03 AM | P | FAIL |
|
|
Approved plans were not available on site, install appears satisfactory, however will need plans for verification.
|
FIR07-00728
| INSP-Sprinkler Rough-in | 10/3/2007 | 10/4/2007 | 10/5/2007 10:29:34 AM | P | PART |
|
|
OH install is good for cover at the drop ceilings, one head at the warehouse restroom is covered, the SW head at the overhead door in not required due to door configuration, final pending ceiling tile and escutcheons.
|
FIR07-00425
| INSP-Sprinkler Rough-in/Hydro | 10/4/2007 | 10/4/2007 | 10/4/2007 3:57:02 PM | P | PART |
|
|
1st and 2nd floor hydrostatic tests passed, OH install is okay for cover at the 3rd floor, no cover allowed on the 4th floor until DSW heads are in place.
|
BLD07-00922
| FIRE-Final Inspection | 10/3/2007 | 10/4/2007 | 10/4/2007 2:57:23 PM | P | FAIL |
|
|
Need to add EM lighting per plan including the exit discharge, post max. occupant load signs as discussed, provide one PFE for the basement level, clear the area blocking access to the basement exit door, need to tag the fire extinguishers with current certification.
|
FIR07-00763
| INSP-Final Inspection | 10/4/2007 | 10/4/2007 | 10/4/2007 1:47:15 PM | P | PASS |
|
|
Fire sprinkler work passed inspection, permit finaled.
|
BLD07-01051
| FIRE-Final Inspection | 10/4/2007 | 10/4/2007 | 10/4/2007 1:02:03 PM | P | CANC |
|
|
Overbooked
|
FIR06-00007
| INSP-Final Inspection | 10/3/2007 | 10/4/2007 | 10/4/2007 12:34:16 PM | A | PART |
|
|
See plans for areas tested on the second floor, noted items in need of correction, HD at the elevator machine room tested okay.
|
FIR07-00755
| INSP-Sprinkler Rough-in/Hydro | 10/3/2007 | 10/4/2007 | 10/4/2007 10:58:06 AM | A | PART |
|
|
Added heads below ductwork are acceptable, okay for cover at the drop ceilings, begin pneumatic testing @ 40psi at 10:15 AM for the preaction system.
|
FIR07-00320
| FIR-Aging Inspection | 10/4/2007 | 10/4/2007 | 10/4/2007 10:24:35 AM | | DEFR |
|
|
wip
|
BLD07-01762
| FIRE-Final Inspection | 10/3/2007 | 10/4/2007 | 10/4/2007 10:24:08 AM | A | PASS |
|
|
Fire life safety passed.
|
FIR07-00348
| INSP-Final Inspection | 10/4/2007 | 10/4/2007 | 10/4/2007 10:21:50 AM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
FIR07-00765
| INSP-Sprinkler Rough-in | 10/3/2007 | 10/4/2007 | 10/3/2007 11:36:28 AM | P | CANC |
|
|
OH cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|
FIR07-00728
| INSP-Sprinkler Rough-in | 10/3/2007 | 10/4/2007 | 10/3/2007 11:36:06 AM | P | CANC |
|
|
OH Cover Inspection Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley Inspection cancelled from web by: Alicia Pauley
|