Inspections for the day of: Tuesday, October 4, 2011.
Number of inspections: 24
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00378 FIR-Aging Inspection10/4/201110/4/201110/6/2011 8:41:54 AM NR
I forwarded this permit number and status to scott for further action.
FIR09-00051 FIR-Aging Inspection10/4/201110/4/201110/6/2011 8:40:57 AM NR
I forwarded this permit number and status to scott for further action.
FIR11-00277 INSP-Alarm Testing10/4/201110/4/201110/4/2011 3:29:50 PMPFAIL
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
FIR11-00274 INSP-Alarm Testing10/4/201110/4/201110/4/2011 3:28:58 PMPFAIL
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
FIR11-00276 INSP-Alarm Testing10/4/201110/4/201110/4/2011 3:27:58 PMPFAIL
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
FIR11-00453 INSP-Alarm Testing10/4/201110/4/201110/4/2011 3:26:55 PMPFAIL
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
FIR11-00279 INSP-Alarm Testing10/4/201110/4/201110/4/2011 3:26:14 PMPFAIL
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
FIR11-00275 INSP-Alarm Testing10/4/201110/4/201110/4/2011 3:25:08 PMPFAIL
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
FIR11-00278 INSP-Alarm Testing10/4/201110/4/201110/4/2011 3:24:32 PMPFAIL
Provide as-builts showing the wiring schematic for the PAM-2 relay that has been added to provide an alarm output to the AES. Also provide a data sheet for the PAM-2 relay. Permit can be finaled when this documentation has been provided.
BLD11-02301 FIRE-Final Inspection10/3/201110/4/201110/4/2011 3:20:59 PMPFAIL
Provide sticker at the main exit, provide single action hardware at the rear exit and provide annual inspection tag for the fire extinguisher.
BLD10-02931 FIRE-Final Inspection10/4/201110/4/201110/4/2011 1:38:55 PMPPASS
life safety passed
BLD09-00832 FIRE-Final Inspection10/4/201110/4/201110/4/2011 1:38:40 PMPPASS
life safety passed
BLD11-00346 FIRE-Final Inspection10/3/201110/4/201110/4/2011 1:38:07 PMAFAIL
Remove the thumbturn dead bolt and round door knob and provide single action hardware on the shop area exterior exit door. Provide single action hardware on the two office doors. Provide self illuminated exit signs as marked on the city approved plans. Mount the fire extinguishers as discussed. Emergency lighting is not required per Carl Madsen.
FIR11-00095 INSP-Final Inspection10/3/201110/4/201110/4/2011 1:21:44 PMACANC
Cancel per Stephan Phone #: ###-####
FIR11-00464 INSP-Sprinkler Rough-in10/3/201110/4/201110/4/2011 12:26:51 PMAPASS
The piping above the hardlids is ok to cover
BLD11-02132 FIRE-Final Inspection10/4/201110/4/201110/4/2011 10:31:49 AMPPASS
life safety passed
BLD11-02144 FIRE-Final Inspection10/3/201110/4/201110/4/2011 10:30:45 AMAPASS
life safety passed
FIR10-00562 INSP-Final Inspection10/4/201110/4/201110/4/2011 10:30:06 AMPPASS
Permit finaled
FIR11-00436 INSP-Sprinkler Rough-in10/3/201110/4/201110/4/2011 9:00:27 AMAPASS
The sprinkler piping in the "lab" room is ok to cover. The plywood sheating that is attached to the roof deck is fire treated. Yesterdays entry to provide upright protection is null and void.
BLD11-01959 FIRE-Final Inspection10/3/201110/4/201110/4/2011 8:29:09 AMAPASS
life safety passed
FIR11-00495 INSP-Final Inspection10/4/201110/4/201110/4/2011 8:28:53 AMAPASS
permit finaled
BLD11-01989 FIRE-Final Inspection10/3/201110/4/201110/4/2011 8:28:37 AMAFAIL
The city approved plans show addtional exit signs that have not been installed. I discussed emergency lighting requirements for the same areas where plan review showed the new exit signs. Will need to verify panic hardware and fire extinguishers as well at next inspection.
BLD11-01888 FIRE-Final Inspection10/3/201110/4/201110/4/2011 8:19:50 AMACANC
life safety passed
FIR11-00382 INSP-Alarm Testing9/29/201110/4/201110/4/2011 12:00:00 AMPCANC
rafe Phone #: ###-####