Inspections for the day of: Thursday, October 4, 2012.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE09-01570 ELE-Aging Inspection10/4/201210/4/201210/10/2012 3:25:33 PM DONE
Called no answer
ELE12-02472 Temporary Service10/4/201210/4/201210/4/2012 3:43:16 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Dan Rohl t/s u/g n ok
ELE12-02468 Rough-In Permanent Service10/4/201210/4/201210/4/2012 3:23:03 PMPFAIL
CALL FOR ACCESS Phone #: ###-#### >> Inspection requested via web by John VanZandt NEC 300.4 NM cable must be protected from physical damage. NEC 314.16B1 Conductor fill in 2 gang box in utility 48 in a 43.5 box
ELE12-02467 Permanent Service10/4/201210/4/201210/4/2012 3:14:22 PMPPASS
Phone #: ###-#### >> Inspection requested via web by John VanZandt p/s o/h rec ok Overhead service drop ok over residential property but only 4 foot above grade up hill from house. should have 10 foot clearence.
ELE12-02462 Final10/4/201210/4/201210/4/2012 3:10:18 PMPPASS
Please inspect the welder outlet, it is installed adjacent to an existing outlet. Please call Cody at ###-#### or Sean at ###-#### with any questions. Thank you and have a wonderful day! Phone #: ###-#### >> Inspection requested via web by Kevin Perez Final ok
ELE12-02429 Electrical Rough-In10/4/201210/4/201210/4/2012 1:34:46 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Ron Zimmerman Rough in cover ok walls only
ELE12-02011 Final10/4/201210/4/201210/4/2012 12:56:43 PMPPASS
Phone #: ###-#### >> Inspection requested via web by Bob Glenn final ok
ELE12-02094 Final10/4/201210/4/201210/4/2012 12:55:32 PMPPASS
CODE 10020 Phone #: ###-#### >> Inspection requested via web by Bob Glenn Final ok
ELE12-01417 Final10/3/201210/4/201210/4/2012 11:56:59 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Thomas Jenkins Final ok
ELE12-01638 Electrical Rough-In10/3/201210/4/201210/4/2012 11:00:39 AMAPASS
Steve. Wall cover. Phone #: ###-#### >> Inspection requested via web by Sean DeLacy Mezz. ceiling rough in cover ok
ELE12-02456 Rough-In Permanent Service10/3/201210/4/201210/4/2012 10:36:38 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Zane Robertson Rough in cover ok p/s u/g n ok
ELE12-01976 Final10/3/201210/4/201210/4/2012 9:40:14 AMAPASS
lock box on hose bib front, 0812
no one is in residence, staged only. will meet up there and move furniture as needed. Phone #: ###-#### >> Inspection requested via web by mike brown Final ok
ELE12-02451 Temporary Service10/3/201210/4/201210/4/2012 8:53:16 AMAPASS
THANK YOU Phone #: ###-#### >> Inspection requested via web by Bob Glenn t/s u/g n ok