FIR12-00291
| INSP-Final Inspection | 10/3/2012 | 10/4/2012 | 10/4/2012 4:19:46 PM | A | PASS |
|
|
Remainder of work passed inspection. Fire alarm permit finaled.
|
FIR12-00314
| INSP-Sprinkler Rough-in/Hydro | 10/3/2012 | 10/4/2012 | 10/4/2012 4:18:49 PM | A | PART |
|
|
Begin 24 hr. air test @ 11:30 AM at 42 psig.
|
BLD12-01438
| FIRE-Final Inspection | 10/3/2012 | 10/4/2012 | 10/4/2012 4:16:40 PM | A | FAIL |
|
|
Refer to fire code review notes regarding exit signs, EM lights, hood permit work, PFE, existing fire sprinkler heads over 50 yrs in service.
|
FIR10-00623
| INSP-Final Inspection | 10/3/2012 | 10/4/2012 | 10/4/2012 4:12:54 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD12-02659
| FIRE-Final Inspection | 10/3/2012 | 10/4/2012 | 10/4/2012 4:08:48 PM | A | PASS |
|
|
Fire life safety passed.
|
FIR12-00198
| INSP-Final Inspection | 10/2/2012 | 10/4/2012 | 10/4/2012 4:06:31 PM | A | NR |
|
|
Need to adjust cd setting at the electrical room, relocate one device at the pharmacy, provide as-built plans for added PIV and notification at the pharmacy, post map and signage at the FACP, provide record of inspection and testing report.
|
FIR12-00068
| INSP-Final Inspection | 9/25/2012 | 10/4/2012 | 10/4/2012 4:02:31 PM | A | PASS |
|
|
Fire alarm permit finaled, inspection passed.
|