InspectorDoug A Poedy
TitleELE-INSPECTOR
Phone #447-7209
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCE12-00148 GCE-Final10/4/201210/4/201210/4/2012 4:05:03 PMPFAIL
Rusty @ ###-####. Numerous pre-existing code violations. High leg on a phase, k/o seals in panel, Bryant breaker in GE panel, bond wire to service nipple size 12 and should be 4.
ELE12-02014 Final10/4/201210/4/201210/4/2012 2:00:13 PMPFAIL
>> Inspection requested via web by Stephanie White. Unable to see any disconnect switches.
ELE12-01856 Final10/4/201210/4/201210/4/2012 1:36:45 PMPPASS
>> Inspection requested via web by Stephanie White
ELE12-01856 Electrical Rough-In10/4/201210/4/201210/4/2012 1:36:23 PMPPASS
>> Inspection requested via web by Stephanie White
ELE12-01885 Electrical Rough-In10/4/201210/4/201210/4/2012 1:23:21 PMPFAIL
mike - call when onsite Phone #: ###-####. Strapping issues everywhere.