ELE19-03715
| Electrical Rough-In | 10/3/2019 | 10/4/2019 | 10/4/2019 2:36:42 PM | P | PASS |
|
|
wall rough-in Phone #: ###-#### Inspection requested via web by Kevin Perez Back offices, Bathroom and breakroom walls only ok to cover
|
ELE19-03760
| Temporary Service | 10/4/2019 | 10/4/2019 | 10/4/2019 1:38:42 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt t/s u/g n ok
|
ELE19-03761
| Temporary Service | 10/4/2019 | 10/4/2019 | 10/4/2019 1:38:27 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Greg Traudt 210.4B Multi wire branch circuit shall be provided with mean to simultaniously disc. all ungrounded conductors(Missing handle tie on 50A GFCI breaker)
|
ELE19-03509
| Electrical Rough-In | 10/3/2019 | 10/4/2019 | 10/4/2019 1:30:59 PM | P | PASS |
|
|
Inspect underground to backfill. Matt Garcia ###-#### Phone #: ###-#### Inspection requested via web by Jeremy Cloud 1in to monument sign, 3in from mech room to service and L.V sleaves to elevator shaft ok to cover
|
ELE19-03699
| Final | 10/4/2019 | 10/4/2019 | 10/4/2019 12:49:06 PM | P | PASS |
|
|
Changing out meter base and riser only due to tree bending riser pipe. Phone #: ###-#### Inspection requested via web by David McClellan p/s o/h rec ok
|
ELE19-03379
| Electrical Rough-In | 10/4/2019 | 10/4/2019 | 10/4/2019 12:35:08 PM | P | PASS |
|
|
Floor heat inspection Phone #: ###-#### Inspection requested via web by Shaun Kirkman master floor heat only ok to cover
|
ELE19-02941
| Temporary Service | 10/4/2019 | 10/4/2019 | 10/4/2019 12:03:13 PM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE19-02527
| Electrical Rough-In | 10/3/2019 | 10/4/2019 | 10/4/2019 11:40:03 AM | A | PASS |
|
|
This is an underground inspection. The electrician is Dan Lowry and he can be contacted at ###-####. Phone #: ###-#### Inspection requested via web by A.M.E. Office public works inspected before back fill
|
ELE19-03643
| Final | 10/3/2019 | 10/4/2019 | 10/4/2019 10:50:17 AM | A | PASS |
|
|
Please call Micah at ###-#### to ensure that we have someone meet you on site. Thanks! Phone #: ###-#### Inspection requested via web by Jesse Simpson final ok
|
ELE19-03215
| Final | 10/3/2019 | 10/4/2019 | 10/4/2019 10:24:34 AM | A | CANC |
|
|
Please call 30 mins prior. Phone #: ###-#### Inspection requested via web by Kerri Hamilton Called in wrong permit
|
ELE19-03563
| Electrical Rough-In | 10/3/2019 | 10/4/2019 | 10/4/2019 10:21:48 AM | A | PASS |
|
|
This is for a hot tub/pool in ground heating cable for concrete slab. If this can be early morning it would be appreciated. The electrician is Patrick Rohm his contact is ###-####. Phone #: ###-#### Inspection requested via web by A.M.E. Office 680.40. Section II of article 680 (680.27c3) does not apply to hot tubs. radiant heat ok to cover
|
ELE19-03765
| Electrical Rough-In | 10/2/2019 | 10/4/2019 | 10/4/2019 9:00:45 AM | A | FAIL |
|
|
Requesting Electrical Rough in Inspection. Thanks Tim ###-#### Phone #: ###-#### Inspection requested via web by Tim Lawrence 330.12 MC cable shall not be exposed to physical damage. (MC shall not be strapped inside metal stud chanels) 330.17, 300.4D MC shall not be secured within 1 1/4in from the face of framing member. ( Multiple places in each area inspected. ) 362.12(8) ENT shall not be exposed to physical damage. (Installed in channel of metal studs.)
|
ELE17-02356
| ELE-Aging Inspection | 10/4/2019 | 10/4/2019 | 10/4/2019 6:31:23 AM | | FAIL |
|
|
Corrections not made final has not been scheduled
|
ELE17-02444
| ELE-Aging Inspection | 10/4/2019 | 10/4/2019 | 10/4/2019 6:30:09 AM | | FAIL |
|
|
Owner has not made attempt to final project.
|