ELE05-03650
| Permanent Service | 10/5/2005 | 10/5/2005 | 10/5/2005 5:07:24 PM | P | NR |
|
|
this is for fire damage, would please like inspection asap so Idaho Power can connect today//call for lock box code//gary ###-#### met contr, and owner, no access to panel and house reflared up while en-route. Too many firemen to make inspection. Told owner to move cabinets, then call elect when ready.
|
ELE05-02260
| Electrical Rough-In | 10/5/2005 | 10/5/2005 | 10/5/2005 4:36:14 PM | P | PART |
|
|
Scheduled by a contractor via Hello! on 10/5/2005 at 9:53:40 AM. Contact: ###-####. ok to cover entry way to ticket counters clg and part of stair walls anop
|
ELE05-01788
| Final | 10/4/2005 | 10/5/2005 | 10/5/2005 4:33:56 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 10/4/2005 at 8:11:29 AM. Contact: ###-####. ok to final
|
ELE05-03583
| Temporary Service | 10/5/2005 | 10/5/2005 | 10/5/2005 3:33:15 PM | P | FAIL |
|
|
heath; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles corrections not made
|
ELE05-03249
| Electrical Rough-In | 10/5/2005 | 10/5/2005 | 10/5/2005 3:22:16 PM | P | PASS |
|
|
gene; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ric ok, p/s u/g n ok
|
ELE05-03253
| Electrical Rough-In | 10/5/2005 | 10/5/2005 | 10/5/2005 3:21:29 PM | P | PASS |
|
|
gene; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa corr made, ric ok, p/s u/g n ok
|
ELE05-03270
| Permanent Service | 10/5/2005 | 10/5/2005 | 10/5/2005 12:34:07 PM | P | PASS |
|
|
rocky; Phone #: ###-#### Internet Inspection Request from: Barbara Moore p/s u/g exst meter cab, ok
|
ELE05-03599
| Electrical Rough-In | 10/5/2005 | 10/5/2005 | 10/5/2005 11:48:21 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 10/5/2005 at 7:23:06 AM. Contact: ###-####. called contr, left corr notice, 312.5 abrasion protection for gec, 250.24(A)(1) gec shall be connected to gnded conductor term or bus, 210.52 recpt shall be on front of dwelling, 110.12(C) there shall be no broken parts, 300.4(A)(1) and (D) 1 1/4" shall be maintained for holes from edge of framing member and nm cable
|
ELE05-03548
| Final | 10/3/2005 | 10/5/2005 | 10/5/2005 10:39:27 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 10/3/2005 at 12:50:52 PM. Contact: ###-####. panels relocated ok, need to check any damper wiring
|
ELE05-02426
| Electrical Rough-In | 10/4/2005 | 10/5/2005 | 10/5/2005 10:36:35 AM | A | PASS |
|
|
Ceiling inspection; Phone #: ###-#### Internet Inspection Request from: Nikki Day called contr to id clg wires, ok to cover clg, panel access needs to be checked
|
ELE05-03621
| Final | 10/3/2005 | 10/5/2005 | 10/5/2005 9:19:52 AM | A | CANC |
|
|
INSTALL A ROOF TOP RECEPTACLE FOR SATELLITE DISH HEATER WITH A FACELESS GFCI RECEPTACLE ABOVE THE PANEL FOR RESETTING PURPOSES. ROOF ACCESS IS IN THE BATHROOM AREA OF THE EDWARD JONES SUITE (SUITE # C). AN 8 FT. LADDER IS NEEDED TO ACCESS THE ROOF HATCH LADDER, SO PLEASE CALL MARK AT MITCHELL ELECTRIC, 30 MINUTES AHEAD OF TIME SO WE CAN MEET YOU THERE. THANKS!!!!-MARK-; Phone #: ###-#### Internet Inspection Request from: Dan Mitchell contr can't meet at job
|
ELE05-03633
| Rough-In Permanent Service | 10/4/2005 | 10/5/2005 | 10/5/2005 8:28:05 AM | A | PASS |
|
|
alan ###-#### ric ok, p/s u/g n ok
|